3.0 ENCLOSURE INSTALLATION
The DS7060 control/communicator and the enclosure are shipped to-
gether. The control, however, still needs to be installed into the enclo-
sure. Hardware for mounting the enclosure to a wall, and the control to
the enclosure is located in its own hardware pack.
3.1 Install the Enclosure
NOTE: This panel is intended for mounting in a restricted access area
and should be wall mounted.
CAUTION: The control panel should only be installed by authorized
service personnel.
Use the enclosure as a template and mark the mounting holes on the
mounting surface.
Pre-start the mounting screws for these holes. Mount the enclosure.
Knock out the desired wire entrances on the enclosure.
3.2 Install the Control/Communicator
CAUTION: The control is static sensitive. Make sure you touch
earth ground before handling the control. This will
discharge any static electricity in your body.
EXAMPLE: Run the ground wire to the enclosure before handling
the control. Then, holding the ground wire (or using a
ground strap), install the control.
Insert the two support posts into the control retainer holes as
shown below in the Support Post Assembly diagram.
Slide the top of the control PCB into the two retainer tabs.
Once in the retainer tabs, the control will rest on the two support
posts.
Secure the bottom of the enclosure by screwing the bottom two
holes through the support posts and through to the control re-
tainer holes.
CAUTION: Once the control is installed, be sure to connect its
ground wire to the top hinge of the enclosure.