3. General Control Programming:
Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, 60 Hz, Auto Bypass disabled and Force Arming
disabled (Program Address 10).
4. Zone Programming:
The Burglar alarm output signal, Address 04, (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
• Program Address 08 must be programmed as [X] [X] [8].
Note: Grade AA requires central station polls of the protected premise unit once every 5 minutes during armed periods and randomly
during disarmed periods. A central station poll once every 24 hours is acceptable for Grade A installations.
Grade B Installations using Digital Alarm Communicator Transmitter with local bell
Required Accessories:
The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
The Ademco Model AB-12 bell/housing (see Section 8.4).
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 32) must be programmed.
AC Failure Report (Program Address 32) must be programmed.
Open Report (Program Address 31) must be programmed.
Close Report (Program Address 31) must be programmed.
Automatic Test Reports (Program Address 36) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Address 23) must be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Address 23) must be programmed for not longer than 60 seconds.
3. General Control Programming:
Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, 60 Hz, Auto Bypass disabled and Force Arming
disabled (Program Address 10).
4. Zone Programming:
The Burglar alarm output signal, Address 04 (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
Program Address 08 must be programmed as [X] [X] [8].
Grade C Installations using Digital Alarm Communicator Transmitter only
Required Accessories:
The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 32) must be programmed.
AC Failure Report (Program Address 32) must be programmed.
Open Report (Program Address 31) must be programmed.
Close Report (Program Address 31) must be programmed.
Automatic Test Report (Program Address 36) must be programmed.
2. Timer Programming:
Entry, Exit Delay Times (Program Address 23) must be programmed for not longer than 60 seconds.
3. General Control Programming:
Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, 60 Hz, Auto Bypass disabled and Force Arming
disabled (Program Address 10).
4. Zone Programming:
The Burglar alarm output signal, Address 04, (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
Program Address 08 must be programmed as [X] [X] [8].