User guide
Page 28 Copyright © 1996-97 Detection Systems, Inc. DS7060 Reference Guide
2. Timer Programming:
• Entry, Exit Delay Times (Program Address 23) must be programmed for not longer than 60 seconds.
3. General Control Programming:
• Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, and Force Arming disabled (Program Address
10).
4. Zone Programming:
• The Burglar alarm output signal, Address 04, (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
• Program Address 08 must be programmed as [X] [X] [8].
Grade A Installations using Digital Alarm Communicator Transmitter with local bell
Required Accessories:
• The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see Section 8.4).
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 32) must be programmed.
• AC Failure Report (Program Address 32) must be programmed.
• Open Report (Program Address 31) must be programmed.
• Close Report (Program Address 31) must be programmed.
• Automatic Test Reports (Program Address 36) must be programmed.
2. Timer Programming:
• Bell Cutoff Times (Program Address 23) must be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Address 23) must be programmed for not longer than 60 seconds.
3. General Control Programming:
• Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, 60 Hz, Auto Bypass disabled and Force Arming
disabled (Program Address 10).
4. Zone Programming:
• The Burglar alarm output signal, Address 04, (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
• Program Address 08 must be programmed as [X] [X] [8].
Central Station Burglary Alarm
The control must be installed in accordance with U. L. Standards UL611 and UL681 for all grades of service.
Grades AA and A Installations using the Applied Spectrum PAL200 and the DACT
Required Accessories:
• The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
• The Applied Spectrum PAL200.
• The Applied Spectrum PAL200 must be installed within 3 feet of the control and the wiring from the Applied Spectrum PAL200 to the
control must be in conduit.
• The Applied Spectrum PAL200 inputs should be connected to the alarm outputs (the active alarm sounder output may be used).
1. Report Programming:
Programming shall be enabled to allow all alarm signals to be transmitted via the DACT and PAL200.
• Burglar Zone Reports are not required since the alarms are transmitted over the PAL200.
• Low Battery Report (Program Address 32) must be programmed.
• AC Failure Report (Program Address 32) must be programmed.
• Open Report (Program Address 31) must be programmed.
• Close Report (Program Address 31) must be programmed.
• Automatic Test Reports (Program Addresses 36) be programmed.
2. Timer Programming:
• Entry, Exit Delay Times (Program Address 23) must be programmed for not longer than 60 seconds.