User guide

DS7060 Reference Guide Copyright © 1996-97 Detection Systems, Inc. Page 27
Entry Delay Timer (Program Address 23) must be programmed for not longer than 60 seconds.
Exit Delay Timer (Program Address 23) must be programmed for not longer than 45 seconds.
C.General Control Programming:
Program Address 10 must be programmed for Swinger Shunt disabled.
Program Address 10 must be programmed as Force Arming disabled.
D.Alarm Output Programming:
Program Address 08 must be programmed as [X] [X] [8] (follow burglar and fire alarm).
Program Address 04 must be programmed as and burglar zones 2 (steady) and fire zones 3 (pulsing).
NOTE: In a system that includes both fire alarm and burglar alarm devices, the system must produce distinct sounds for fire and burglar
alarm conditions either by using different indicating appliances or by using distinct cadences for the same appliance.
Local Burglary Alarm
The control must be installed in accordance with U. L. Standards UL681 and UL609 for all grades of service.
Grade A Installations using Digital Alarm Communicator Transmitter with local bell
Required Accessories:
The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
The Ademco Model AB-12 bell/housing (see Section 8.4).
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 32) must be programmed.
AC Failure Report (Program Address 32) must be programmed.
Open Report (Program Address 31) must be programmed.
Close Report (Program Address 31) must be programmed.
24-Hour Check-In Reports (Program Address 36) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Address 23) must be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Addresses 23) must be programmed for not longer than 60 seconds.
3. General Control Programming:
Must be programmed for Swinger Shunts disabled, Closing Ringback disabled, 60 Hz, Auto Bypass disabled and Force Arming
disabled (Program Address 10).
4. Zone Programming:
The Burglar alarm output signal, Address 04, (whether pulsed or steady) must be different from the Fire alarm signal.
5. Alarm Output Programming:
Program Address 08 must be programmed as [X] [X] [8].
Police Station Connection
The control must be installed in accordance with U. L. Standards UL611 and UL681 for all grades of service.
Grades AA and A Installations using the Applied Spectrum PAL200 and the DACT
Required Accessories:
The control must be mounted in the Detection Systems’ model 7060CC enclosure with a cover actuated tamper switch installed.
The Applied Spectrum PAL200.
The Applied Spectrum PAL200 must be installed within 3 feet of the control and the wiring from the Applied Spectrum PAL200 to the
control must be in conduit.
The Applied Spectrum PAL200 inputs should be connected to the alarm outputs (the active alarm sounder output may be used).
1. Report Programming:
Programming shall be enabled to allow all alarm signals to be transmitted via the DACT and PAL200.
Burglar Zone Reports are not required since the alarms are transmitted over the PAL200.
Low Battery Report (Program Address 32) must be programmed.
AC Failure Report (Program Address 32) must be programmed.
Open Report (Program Address 31) must be programmed.
Close Report (Program Address 31) must be programmed.
24-Hour Check-In Reports (Program Address 36) must be programmed.