User guide
Page 26 Copyright © 1996-97 Detection Systems, Inc. DS7060 Reference Guide
burglary = steady). In all cases, the special emergency keys must be silent.
• The ground start feature shall not be programmed.
• Compatible keypads are Detection Systems’ DS7443, DS7445, and DS7447.
• The Pager format must not be employed.
• The alarm output must not be delayed.
8.3 Programming the DS7060
When used in U. L. Listed Requirements, the control must conform to certain programming requirements. The following is a list of the
required program entries and required accessories for specific U. L. Listed Requirements.
Household Fire Alarm (using Digital Alarm Communicator Transmitter with local bell)
The control must be installed in accordance with NFPA 72.
Required Accessories:
• At least one Detection Systems’ model DS250 Series 4 wire smoke detector with an MB4W Series 4 wire base, or another Listed 4
wire smoke detector.
• One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide 85dB for UL985 and NFPA 72 requirements; other Listed compatible devic-
es with a voltage range of 10.2 to 14.0 V may be used) is required for this application and must be installed inside the protected area.
• The standard control enclosure can be used.
• At least one DS7443, DS7445 or DS7447 Keypad must be used.
• Four-wire detectors must be used with Listed power supervision devices. A compatible Listed four-wire detector is the Detection Sys-
tems, Inc. DS250 in an MB4W base. A compatible Listed EOL relay is the Detection Systems, Inc. EOL200.
• All zones must be used with the EOL resistor (P/N 25899) provided.
A. Report Programming:
• Fire Zone Report must be programmed.
• Low Battery Report (Program Address 32) must be programmed.
• AC Failure Report (Program Address 32) must be programmed.
B.Timer Programming:
• Bell Cutoff Time (Program Address 23) must be programmed for not less than 4 minutes.
C.Zone Programming:
• For household fire installations only, the output signal may be pulsed or steady. For a combination system, see the selection below
on alarm output programming. Fire zones must be programmed (Address 03 - Zone Action) for alarm on short, trouble on open
(value = 1).
D.Alarm Output Programming:
• Program fire zone outputs as pulsed, burglar zone outputs as steady (Address 04).
E.General Control Programming:
• Program Address 10 must be programmed for Closing Ringback Enabled.
• Program Address 10 must be programmed for 60 Hz.
• Program Address 10 must be programmed for Swinger Shunt disabled.
• Program Address 10 must be programmed as Force Arming disabled.
• Program Address 10 must be programmed for Auto Bypass disabled.
Grade A Household Burglary Alarm (using Digital Alarm Communicator Transmitter with local bell)
The control must be installed in accordance with U. L. Standard UL1641.
Required Accessories:
• At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other Listed compatible devices with a voltage range of 10.2 to 14.0 V may be
used) is required for this application.
• The standard DS7060 enclosure can be used.
A.Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 32) must be programmed.
• AC Failure Report (Program Address 32) must be programmed.
B.Timer Programming:
• Bell Cutoff Time (Program Address 23) must be programmed for not less than 4 minutes.