8.0 INSTALLATION GUIDE FOR U. L. LISTED SYSTEMS
8.1 DS7060 U. L. Listings
Household Fire Alarm, U. L. Standard UL985
Household Burglary Alarm, U. L. Standard UL1023
Police Station Connection Grades AA and A, U. L. Standard UL365
Central Station Burglary Alarm Grades AA, A, B, and C, U. L. Standard UL1610
The control panel has not been investigated to the requirements of UL294.
The control panel should be installed in accordance with U. L. Standard UL681, Installation and Classification of Mercantile and Bank
Burglar Alarm Systems, or U. L. Standard UL1641, Installation and Classification of Residential Burglar Alarm Systems. It should also be
installed in accordance with NFPA 72 for Household installations.
The following table shows the DS7060 system configuration for the various types of fire and burglar alarm service for which the products are
U. L. Listed.
8.2 Installation Considerations
Failure to install and program the control in accordance with the requirements in this section voids the listing mark of Underwriters Lab-
oratories, Inc.
The standby battery capacity is 7 AH @ 12 VDC.
The total nominal current must not exceed 750 mA when on standby or in alarm.
The control must be mounted indoors and within the protected area.
Enclosure tamper switches (if used) must be connected to a 24-hour zone.
Grounding must be in accordance with article 250 of the NEC (NFPA 70).
At least one U. L. Listed keypad with zone display must be connected.
Zones must be connected to U. L. Listed, compatible devices.
50 Hz AC input cannot be used in U. L. Listed Requirements.
The ground wire provided with the enclosure must be connected between the “Earth GND” connection on the control and the enclo-
sure tab.
The keypad panic alarm output must follow the corresponding zone’s programming (e.g. fire = pulsing [or steady if not a combination],