User guide
Page 14 Copyright © 1996-97 Detection Systems, Inc. DS7060 Reference Guide
7.10 Address 10 - General Control
• Siren on Comm. Fail for Silent Zone: If programmed, a silent zone will sound the alarm outputs if the zone is in an alarm condition
and the system fails to communicate with the central station.
• Closing Ringback: If programmed, the keypad sounders and Output 3 will activate for 2 seconds after the system is armed and the
closing report is successfully sent. This requires Closing Ringback and Closing Report to be programmed.
• Swinger Shunt: If enabled, a zone can only alarm or trouble up to three times per armed period. After the third alarm or trouble, the
zone will be bypassed and a bypass report for this zone will be sent. Fire zones are never swinger shunted.
• 50 Hz/60 Hz: Set to local power type. The panel clock is synchronized to the power line frequency. 60 Hz required for U.L. Listed Re-
quirements.
• Keypad Mode: Commercial Mode requires a PIN number for all functions. Residential Mode only requires a PIN number for disarm-
ing and silencing alarms.
• Quick Arm: If enabled, a PIN is not needed to arm. Note: Used only in conjunction with commercial mode.
• Easy Exit: If the system is armed and there have been no zones violated, then you can reenter a Quick Arm Command without first
disarming the system. This allows you to change the arming level or to restart the exit delay so you can exit through an entry/exit zone.
• Force Arming Limit: If enabled, the system can be armed when zones are violated or if an AC power falure has occurred, by pressing
the [Bypass Key] after an arming command. If bypassing is not allowed, a three beep error tone will sound and the panel will return to
standby mode. Note: If “Auto Bypass” (Address 10) is enabled, arming the panel will automatically bypass the corresponding number
of zones programmed into Force Arming Limit. If “Auto Bypass” is disabled, any zones that were programmed to be bypasses in Ad-
dress 02, may be Auto Bypassed.
• Auto Bypass: If enabled, the system will automatically bypass faulted zones when an arming command is used. If bypassing is not
allowed on the “Not Ready” zone, a three beep error tone will sound, and the panel will return to standby mode. Note: When enabling
Auto Bypass, it may be desirable to program “Force Arming Limit” (Address 10). If “Force Arming Limit” is set to 0, Auto Bypass will al-
low bypassing of any zone that was programmed to be bypassed by Address 02. If “Force Arming limit” is programmed between 1 and
6, this is the maximum number of zones that can be Auto Bypassed.