Chime Mode (#7) does not work
when a zone is faulted.
Some functions won’t work on a Mas-
ter keypad.
a) Not activating for interior zones.
b) The keypad is not assigned to the same
partition as the zone being activated.
Some functions require you to enter single
partition mode when using a Master key-
pad.
a) Chime mode only activates for perimeter zones -
Chime mode must be programmed. Also, if the
perimeter zone has trouble enabled (trouble on
open), the chime won’t work if that zone is open-
ing.
b) Chime mode will only activate the sounder on key-
pads that are assigned to the same partition as
the zone.
The following commands require that you are in Sin-
gle Partition Mode when entering from a Master key-
pad:
History read-back
Chime mode
Checking zone status
Checking zone trouble status (after #87 - Master
keypad will show only partition name)
Bypassing zones
Symptom Probable Cause Possible Solution
Keypad Problems (Continued)
17.2 Reporting Problems
Won’t send open or close reports.
Reports for partitions 2-8 are being
sent with partition 1’s reporting ID.
Not getting AC power fail reports.
Panel never transmits history to WD-
SRP.
The communicator test report is not
being sent.
Not programmed correctly.
The account codes for 2-8 are not pro-
grammed or are not programmed correctly.
a) AC power fail messages are sent only
with other reports, such as low battery.
b) Check A/C report offset (0197). If 00, A/
C report will work like above, if another
number, A/C report will be delayed.
a) Not programmed to send history.
b) Time and date not set.
a) Report not programmed properly.
b) There was a control problem at the time
the report should have been sent. If this
is the case, the communicator test re-
port will not be sent. Instead, the con-
trol will send the “System Off Normal”
report.
Check addresses: 0320, 0321, 0323, and 0187.
Check addresses: 0496-0526.
a) Try forcing another report to send when AC is not
present.
b) Wait until the delay times out or set to a lower
number if desired.
a) Check programming.
b) Verify that the time in the panel is set.
a) Check programming addresses 1521, 1522,
1525, and 0329.
b) Program “System Off Normal” report in address
0336.
Symptom Probable Cause Possible Solution
17.3 Zone Problems
Fire Alarm displays on keypad but
no zone numbers are displayed.
Every other zone displays Not
Ready.
In Commercial Fire Mode, fire alarms must
be silenced before the zone number will
display.
Zone Programming is incorrect.
Enter a valid disarm PIN and press #, then enter a
valid disarm PIN and press # again to display the
zones.
Program as a multiple zone input for DS7432 or
DS7460, a single zone input for contacts and sen-
sors, or program as a DS7465.
Symptom Probable Cause Possible Solution