Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 68
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Fire Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 0325) must be programmed.
AC Failure Report (Program Address 0327) must be programmed.
Open Report (Program Address 0320) must be programmed.
Close Report (Program Address 0321) must be programmed.
24-Hour Check-In Reports (Program Addresses 0329 and 0336) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Addresses 0195 and 0196) must be programmed for not less than 5 minutes.
Entry, Exit Delay Times (Program Addresses 0191-0193) must be programmed for not longer than 60 seconds.
3. General Control Programming:
Must be programmed for no swinger shunts (Program Address 0000 data digit 2, enter 0, 1, or 2).
Program Address 0185 must be programmed as: Data Digit 1=0, Data Digit 2=0.
4. Commercial Fire Mode Programming:
Local (Program Address 0186, data digit 1, enter as a 1 through 6).
Central Station (Program Address 0186, data digit 1, enter as a 7 through *2).
The keypad panic functions are not intended to be a substitute for Listed manual pull boxes.
13.6 Wiring and Programming information for installations using the Ademco AB-12 Bell/Housing
Control/Communicator
DS7400Xi
Cut this jumper
JP1
123 546
To control Alarm Output +
To control Alarm Output –
To control Zone 8 Input
To control Loop Positive
To control Earth Ground
EOL
27K
BELL
Bell Tampers
Outer Bell Box
Inner Bell Box Lining
Ademco AB-12 Bell/Housing
Terminal 1
Terminal 29 (+)
Terminal 30 (8-)
Terminal 5 (-)
Terminal 6 (A)
Alternate EOL (if not
using a Fire card)
Detection Systems’
P/N 28300
1) Disconnect the wire jumper from terminal 4 to the inner housing of the Bell Box (prevents a ground fault condition).
2) Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, cut the jumper wire “JP1” on the
control. The EOL used in the AB-12 Bell/Housing must be 27K ohms.
3) Program Zone 8 as a 24-hour zone by programming it to follow zone function 7. (Program address 0025 = 07).
4) Do not change the default programming of zone function 7. (Program address 0007 should be 22).