Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 66
4. Alarm Output Programming:
Program Address 0146 must be programmed as: Data Digit 1=6, Data Digit 2=3.
Program Address 0149 must be programmed as: Data Digit 1=8.
NOTE: In a system that includes both fire alarm and burglar alarm devices, the system must produce distinct sounds for fire and burglar
alarm conditions either by using different indicating appliances or by using distinct cadences for the same appliance.
13.4 General System Requirements
Applies to the following grades only:
Local Burglary Alarm - Grade A using Digital Alarm Communicator Transmitter (DACT)
Police Station Connection - Grades AA and A using DACT and ARDIS interface module.
Grade A using DACT and local Bell.
Central Station Burglary Alarm - Grades AA and A using DACT and ARDIS interface module.
Grade B using DACT and local bell.
Grade C using using Digital Alarm Communicator Transmitter only.
The controls must be installed in accordance with U. L. Standards UL681 and UL609 for all grades of service.
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 0325) must be programmed.
AC Failure Report (Program Address 0327) must be programmed.
Open Report (Program Address 0320) must be programmed.
Close Report (Program Address 0321) must be programmed.
24-Hour Check-In Reports (Program Addresses 0329 and 0336) must be programmed.
2. General Control Programming:
Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
Program Address 0185 must be programmed as: Data Digit 1=0, Data Digit 2=0.
3. Zone Function Programming:
The Burglar alarm signal (whether pulsed or steady) must be different from the Fire alarm signal.
4. Alarm Output Programming:
Program Address 0146 must be programmed as: Data Digit 1=6, Data Digit 2=3.
Program Address 0149 must be programmed as: Data Digit 1=8.
13.4.1 Local Burglary Alarm
A. Grade A Installations using Digital Alarm Communicator Transmitter with local bell
Follow General System Requirements as listed in 13.4.
Required Accessories:
The control must be the Detection System’s model DS7400XiCC with a cover actuated tamper switch installed.
An Ademco Model AB-12 bell/housing* (see section 13.6).
1. Timer Programming:
Bell Cutoff Times (Program Addresses 0195 and 0196) must be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Addresses 0191-0193) must be programmed for not longer than 60 seconds.
13.4.2 Police Station Connection
Follow General System Requirements as listed in 13.4.
Required Accessories:
The control must be the Detection Systems’ model DS7400XiCC with a cover actuated tamper switch installed.
An ARDIS (or DataTAC) interface module.
• The ARDIS module and antenna should be mounted within the protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
1. Timer Programming:
Entry, Exit Delay Times (Program Addresses 0191-0193) must be programmed for not longer than 60 seconds.