Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 64
13.0 Installation Guide for U.L. Listed Systems
13.1 DS7400Xi U. L. Listings:
• Household Fire Alarm, U. L. Standard UL985
• Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Type Initiating: Automatic, Manual, Sprinkler Superviso-
ry, and Waterflow), U. L. Standard UL864
• Household Burglary Alarm, U. L. Standard UL1023
• Police Station Connection Grades AA and A, U. L. Standard UL365
• Central Station Burglary Alarm Grades AA, A, B, and C; U. L. Standard UL1610
The control panel should be installed in accordance with U. L. Standard UL681, Installation and Classification of Mercantile and Bank
Burglar Alarm Systems, or U. L. Standard UL1641, Installation and Classification of Residential Burglar Alarm Systems. It should also be
installed in accordance with NFPA 72 for Household and Commercial Fire installations.
13.1.1 U.L System Configurations
The following table shows the DS7400Xi system configuration for the various types of fire and burglar alarm service for which the product
is U. L. Listed.
Product
R
1
1
R
R
4
0
0
0
2
0
4
0
n/a
U. L. Application
CSF-D CSF-D/RF LF CSB-A CSB-B/C LB-A PSCB-D-A PSCB-RF-A HF/B
DS7400Xi
Standard Enclosure
Attack Enclosure
AE-TR16 Enclosure
DS7416
DS7420i
DS7430
DS7432
DS7433
DS7447
DS7460
DS7481
DS7488
AB12 Bell w/Housing
R
1
1
R
n/a
R
0
0
0
2
0
n/a
0
n/a
R
1
1
R
n/a
R
0
0
0
2
0
n/a
0
n/a
R
n/a
R
n/a
R
4
0
0
0
3
0
4
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
R
n/a
R
n/a
R
4
0
0
0
3
0
4
0
R
R
1
1
n/a
n/a
n/a
0
0
0
3
0
n/a
0
n/a
Configuration Codes
R = Required
0 = Optional
n/a = Not Applicable
1 = Standard or attack enclosure may be
used.
2 = Either enclosure may be used. Device
must be mounted to the enclosure cover,
or within 20 ft. w/wiring in conduit.
3 = Either enclosure may be used.
4 = Either the DS7420i or the DS7481
must be used to monitor the phone line
input to the control unit.
Key to Application Codes
CSF-D = Central Station Fire w/ DACT (Digital Alarm Communications Transmitter/dialer)
CSF-D/RF = Central Station Fire w/ DACT and Radio (ARDIS System)
LF = Local Fire
CSB-A = Central Station Burglary, grades AA and A
CSB-B/C = Central Station Burglary, grades B and C
LB-A = Local Burglary, grade A
PSCB-D-A = Police Station Connected Burglary w/DACT, grade A
PSCB-RF-A = Police Station Connected Burglary w/Radio (AAGARD System - DS7416),
grades AA and A
HF/B = Household (residential) Fire and Burglary
13.2 INSTALLATION CONSIDERATIONS
• Failure to install and program the control in accordance with the requirements in this section voids the listing mark of Underwriters
Laboratories, Inc.
• The standby battery capacity is 35 AH @ 12 VDC.
• The total nominal standby current must not exceed 1.5 A nor 2.5 A when in alarm.
• The control must be mounted indoors and within the protected area.
• Enclosure tamper switches (if used) must be connected to a 24-hour zone.
• Grounding must be in accordance with article 250 of the NEC (NFPA 70).
• At least one U. L. Listed keypad with zone display must be connected.