Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 56
12.33.1 Output Function Partition Assignment: Program Addresses (3733-3740)
Data Digit 1 Data Digit 2
Function 1 Function 2
Program Address 3733
Data Digit 1 Data Digit 2
Function 3 Function 4
Program Address 3734
Data Digit 1 Data Digit 2
Function 9 Function 10
Program Address 3737
Data Digit 1 Data Digit 2
Function 11 Function 12
Program Address 3738
Data Digit 1 Data Digit 2
Function 5 Function 6
Program Address 3735
Data Digit 1 Data Digit 2
Function 7 Function 8
Program Address 3736
Data Digit 1 Data Digit 2
Function 13 Function 14
Program Address 3739
Data Digit 1 Data Digit 2
Function 15 Must Be 0
Program Address 3740
1
2
3
4
5
6
7
Belongs to Partition 1
Belongs to Partition 2
Belongs to Partition 3
Belongs to Partition 4
Belongs to Partition 5
Belongs to Partition 6
Belongs to Partition 7
Belongs to Partition 8
Select Option DD
8Follows all Partitions
0
0
12.34 Dual Phone Line/Bell Supervision Module Output Programming: Program Address (1520)
Example:
To program the Dual Phone Line/Bell Supervision
Module to supervise Phone Line 1 and Phone Line 2.
Data Digit 1 = [2], Data Digit 2 = [0].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [1] [5] [2] [0]
Enter Data Digit 1: [2]
Enter Data Digit 2: [0]
Enter the pound key: [#]
Program the next Address, Program a different
Address, or Exit the Programmer’s Mode.
0
Options
Disabled
0 1 2 3 4 5 6 7 8 9
Bell Monitor
Phone Line 1 Monitor
Phone Line 2 Monitor
Alarm Output on line fault
Enter the Data Digit as a:
Data Digit
1
Data Digit 2
must be a 0.
2
The Dual Phone Line/Bell Supervision Module is the DS7420i.
See section 1.13 for further details.
When in Central Station or Local Commercial Fire Mode, this address will be
forced to specific values (see section 12.15.1 and 12.15.2).