Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 47
12.23 DS7412 RS232 Interface Control Programming: Program Address (0206)
Example:
To program to enable the DS7412 and send Open/Close Reports to the
printer.
Data Digit 1 = [1], Data Digit 2 = [2].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [2] [0] [6]
Enter Data Digit 1: [1]
Enter Data Digit 2: [2]
Enter the pound key: [#]
Program the next Address, Program a different Address, or Exit the
Programmer’s Mode.
Select Options 1 2 3 4 5 60
No Events
Alarms, Troubles, and Restorals
Opens and Closes
All Other Events
7
Enter the Data Digit as a:
Data Digit
12
DD
DS7412 Disabled
0
DS7412 Enabled
1
Select Option
DS7412 RS232 Interface Control Programming allows you to enable or
disable the DS7412 and to select which history events are sent to the
printer as they occur. Selecting “No Events” will cause the history to be
printed only on command.
To print the History Buffer starting from the most recent event, enter the
Master Code followed by [#] [0] [8]. To stop printing, enter Master Code
[#] [0] [8] again.
Note: If using the WDSRP Direct
Connection option for pro-
gramming, Address 0206
must be set for 1 0. Address
0207 must be set for 2 5.
12.24 DS7412 RS232 Interface Configuration Programming: Program Address (0207)
Example:
To program a 1200 Baud printer for No Parity, Soft-
ware Flow Control, 2 Stop Bits and 8 Data Bits.
Data Digit 1 = [1], Data Digit 2 = [2].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [2] [0] [7]
Enter Data Digit 1: [1]
Enter Data Digit 2: [2]
Enter the pound key: [#]
Program the next Address, Program a different Ad-
dress, or Exit the Programmer’s Mode.
Select Options 0 1 2 3 4 5 6 7
No Parity
ODD Parity
EVEN Parity
Software Flow Control
8 Data Bits
0
Hardware Flow Control
Enter the Data Digit as a:
1 Stop Bit
2 Stop Bits
DD
300 Baud
0
1200 Baud
2400 Baud
1
2
4800 Baud
3
12
Select Option
Data Digit
9600 Baud
4
14400 Baud
5
DS7412 RS232 Interface Configuration Programming allows you to
configure the DS7412 for your printer. Most printers will operate us-
ing the default values for the DS7412. Some printers may operate
more efficiently using optional program values.
Consult the operating guide provided with your printer to be sure that
its configuration matches the one programmed here.
Note: If using the WDSRP Direct Connection option for program-
ming, Address 0206 must be set for 1 0. Address 0207 must
be set for 2 5.