Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 43
12.15 Commercial Fire Mode Programming: Program Address (0186)
Example:
To program the Commercial Fire Mode parameters as: Central Station
Commercial Fire Mode enabled, with a 10 second delay on Waterflow
Zones, having the Bell and Aux. activate on Fire Alarms, and using
California March Time.
Data Digit 1 = [8], Data Digit 2 = [1].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [1] [8] [6]
Enter Data Digit 1: [8]
Enter Data Digit 2: [1]
Enter the pound key: [#]
Program the next Address, Program a different Address, or Exit the
Programmer’s Mode.
Enter the Data Digit as a:
Select Options 0 1 2 3 4 5 6 7 8
Commercial Fire Mode disabled
Local Comm. Fire Mode enabled
10 sec. delay on waterflow zone
20 sec. delay on waterflow zone
30 sec. delay on waterflow zone
40 sec. delay on waterflow zone
50 sec. delay on waterflow zone
9 *0 *1 *2
Central Station Comm. Fire Mode enabled
*0 - *2 are Hex values. They will display as A - C at the keypads.
Zones 1-4 may only have waterflow delays.
Enter the DD as a:
Select Options
Bell and Aux. activate on Fire
Bell and Aux. activate on Burg
Pulsing Fire Alarms are 1 sec. On / 1 sec. Off
Pulsing Fire Alarms use Temporal Cadence
Pulsing Fire Alarms use California March Time
0 1 2 3 4 5
Data Digit
1
2
This section describes how to define the parameters for
the Commercial Fire Mode.
See Glossary (section 7.10) for further details.
When programming Fire zones, it is recommended that they be zone functions 12 and 13 (see sections 12.2 and 12.15.3).
12.15.1 When Central Station Commercial Fire Mode is chosen, address 1520 (DS7420i: Dual Phone Line/Bell Supervision Module
Output Programming),will be forced to a value of 5.
12.15.2 When Local Commercial Fire Mode is chosen,address 1520 (DS7420i: Dual Phone Line/Bell Supervision Module Output
Programming),will be forced to a value of 3, 4, or 5. (Turns the Bell Monitor feature ON and the Alarm Output on Line Fault feature OFF)
12.15.3 Regardless of which Commercial Fire Mode is chosen, the following parameters will be forced when exiting local programmer’s
mode:
Zone Function 12, address 0012, will be a 7 *0.
Zone Function 13, address 0013, will be a 7 *1.
Zone Function 14, address 0014, will be a 7 *2.
Zone Function 15, address 0015, will be a 7 *3.
Zone Bypass address 0017 will not allow zone functions 12 - 15 to be bypassed.
Emergency Key, address 0181, data digit 1, will become a 3 if programmed previously as a 2. Data digit 2 will become a 2 if programmed
previously as a 3.
Panic Key, address 0182, data digit 1, will become a 2 if programmed previously as a 3.
Fire Bell Cutoff: If less than 5, set to 5, otherwise untouched.
12.15.4 In Central Station Commercial Fire Mode, the following communication parameters will be forced:
Report Codes: If 0, the following defaults will be set, otherwise they will be unchanged.
0256
0257
0269
0270
0271
Address
*0 1
7 1
*0 3
*0 4
*0 5
Default
0272
0286
0287
0288
0289
Address
*0 6
7 3
7 4
7 5
7 6
Default
0325
0301
0302
0303
0304
Address
6 9
6 3
6 4
6 5
6 6
Default
0326
0327
0328
0329
0330
Address
7 9
6 *0
7 *0
8 3
7 *5
Default
0331
0334
0335
0336
Address
6 *5
3 9
3 *0
3 9
Default
Phone Control: If 0, set to 6 1, 4/2 @ 18/23, 10pps, otherwise untouched.
Test Report: Set to 8, call out every day.