Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 1995-96 Detection Systems, Inc. Page 18
• Commercial Fire Mode: When in Commercial Fire Mode, the
control panel will perform some functions (e.g. communications)
differently to conform with commercial fire regulations.
- See Commercial Fire Mode Programming, program address
0186.
• Water Flow Zone Delay: This is the amount of time a water flow
zone must be violated before the control panel will initiate an alarm.
- The delay is necessary to accommodate normal changes in
water pressure.
- If the water flow initiating device incorporates its own time de-
lay, do not program the control panel unit to exceed 120 sec-
onds combined time delay.
• Pulsing Fire Zone: This is a zone programmed to output a pulse
for a fire alarm in the normal manner (one second ON, one sec-
ond OFF).
• California March Time: This is a zone programmed to output a
pulse for a fire alarm in the California Time cadence (ten 1/2 sec-
ond pulses, followed by one second of quiet time).
• Temporal: This is a zone programmed to output a pulse for a fire
alarm in the Temporal cadence (three 1/2 second pulses, followed
by one second of quiet time).
• Single Keypad Use: The keypad should be used on the keypad
bus and be mounted to the front of the control enclosure OR if
within the same room as the control equipment with the wire run
in conduit (or equivalently protected against mechanical injury)
within 20 ft. (6.1 m) of the control equipment.
- This keypad should be assigned as address 1.
• Multiple Keypad Use:
One keypad only must be used on the
option bus, at any address from 11 - 14, and must meet the fol-
lowing requirements:
- The keypad must be mounted to the front of the control enclo-
sure OR mounted within the same room as the control equip-
ment and the wire is run in conduit (or equivalently protected
against mechanical injury) within 20 ft. (6.1 m) of the control
equipment.
- All other keypads should be connected to the keypad bus and
may be placed as needed (within the noted wiring limitations in
the installation manual).
- One keypad must be assigned as address 1.
7.12 Open/Close Report Control Programming
• Open and Close Reports: If programmed, these reports are
sent when the system is armed or disarmed. They may be sent
independently for the opening and closing of each partition, or the
first partition to open and the last partition to close may send the
reports.
• Send Trouble at Close for Bypassed Zones: If programmed, a
trouble report will be sent for each zone bypassed when the sys-
tem is armed.
• Alternate between both Phone Numbers: If programmed, open
and close reports will be sent to phone number one first. If phone
number one does not pick-up, the control panel will alternate to
phone number two. If phone number two does not pick-up, the
control panel will alternate back to phone number one. It will alter-
nate between both phone numbers until successful.
7.13 Report Programming
• Reports: For pulse formats, reports are programmed by entering
data in the reporting and extended digits. The report will send the
data programmed for each event. For SIA and Contact ID, the
report formats are fixed and may be activated by placing a 1 in
the reporting digit.
- To disable a report, enter a 0 in the reporting digit.
- To send the Man No. along with Open and Close reports, pro-
gram an "F" (enter [*] [5] at the keypad) in the extended digit.
• Keypad Fire Alarm: This report is sent when a fire alarm has
been activated by the “A” emergency key.
• Keypad Fire Restoral: This report is sent when a keypad fire
alarm has been restored using the [System Reset] command.
• Zone Function Alarm: An alarm report is sent when a zone alarm
occurs. Alarm reports are enabled by zone function. Program this
report for any zone functions you wish to send an alarm report
about. For local zones (no reports), do not program an alarm re-
port. The zone number will automatically be sent for this report in
SIA or Contact ID format.
• Keypad Emergency Alarm: This report is sent when an emer-
gency alarm has been activated using the “B” emergency key.
• Keypad Panic: This report is sent when an emergency alarm
has been activated using the “C” emergency key.
• Zone Function Restoral: This report is sent when the zone alarm
and trouble conditions are cleared. The zone number will auto-
matically be sent for this report in SIA or Contact ID format.
• Zone Function Trouble: This report is sent when a zone trouble
condition occurs. This can be an open circuit, if the zone is pro-
grammed for “trouble on open”, a multiplex tamper switch being
activated, or a multiplex zone not communicating with the control
panel. The zone number will automatically be sent for this report
in SIA or Contact ID format.
• Open: This report is sent when the system has been disarmed.
In SIA or Contact ID formats, the user number for the person who
disarmed the system will be sent with this report. To send the user
number along with an Open report in other formats, program the
extended digit of the report as *5. In Contact ID format, the parti-
tion number will also be sent along with this report. The Open
report will only be sent if a Close report was sent previously.
• Close: This report is sent when the system has been armed. In
SIA or Contact ID formats, the user number for the person who
armed the system will be sent with this report. To send the user
number along with a Close report in other formats, program the
extended digit of the report as *5. In Contact ID format, the parti-
tion number will also be sent along with this report.
• Duress: This report is sent when the system is disarmed using a
duress code. The user number will not be sent along with this
report.
• Partial Close: This report is sent when the system is armed par-
tially, or force armed.
• First Open After Alarm: This report is sent when the system is
disarmed after an alarm has occurred. It will also be sent if the
system is already disarmed and a user number is entered to si-