Reference Guide for the DS7400Xi (Version 3+) Control/Communicator Armed Armed Perimeter Status Status Supervisory Power Bell Silenced Fire Trouble ® Power Fire ® 1 2 3 4 5 6 7 8 On On 1 2 3 Off 1 2 3 Off 4 5 6 Perimeter Only 4 5 6 Perimeter Only 7 8 9 No Entry 7 8 9 No Entry * 0 # Bypass * 0 # Bypass System Reset System Reset Keypad Quick Reference Guide Turning On (arming) your System Commands for other System Features Normal Arming - [PIN] + [On] Chime
Table of Contents Keypad Quick Reference Guide 1 1.0 Specifications 4 1.1 Enclosure Housing 1.2 Temperature 1.3 Power 1.4 Outputs 1.5 Zones 1.6 Keypads 1.7 Communicator 1.8 Partitions 1.9 Users 1.10 Lightning Protection 1.11 Burglar/Fire Zone Inputs 1.12 Fire Signal Initiating Circuit (2-wire mode) 1.13 Multiplex Bus Wiring Requirements 1.14 Option Bus Wiring Requirements 1.15 Max. Load Currents 1.16 Backup Battery Calculation 1.17 Standby Current Load 1.18 Options 2.0 Enclosure Installation 2.
12.2 Zone Function Programming: Program Addresses (0001-0015) 35 12.3 Zone Programming: Program Addresses (00180145) 36 12.4 Zone Partition Assignment: Program Addresses (1248-1311) 36 12.5 Zone Bypass Programming: Program Addresses (0016-0017) 37 12.6 Output Programming: Program Addresses (01460148) 38 12.7 Output Partition Assignment: Program Addresses (0149-0150) 38 12.8 Partition Control Programming: Program Address (0165) 39 12.9 Quick Arm Control Programming: Program Address (0169) 39 12.
AWG) are recommended on any 1000 foot (305 m) run. NOTE: Shared cable is not recommended for keypad, multiplex, options bus, telephone, or siren wiring. 1.0 Specifications 1.1 Enclosure Housing 1. The standard enclosure is manufactured from 20 Ga., cold-rolled steel, and measures 12.5" Wide, by 14.5" High, by 3" Deep (31.8 cm Wide, by 36.8 cm High, by 7.6 cm Deep).
1.
• DS7433: • DS7445: • DS7447: 8 Input Direct Module (1 per system. Can not be used with the DS7430 Multiplex Expansion Module). The DS7433 provides a means of expanding the system to include eight additional hard-wired zones. Each zone can support up to twenty 2-wire smoke detectors (can also support 4-wire smoke detectors). • Current Draw = 65 mA, Standby. 80 mA, Alarm. Add 15 mA for each additional zone in alarm. Control Station.
2.2 Install the Control/Communicator 2.0 Enclosure Installation The DS7400Xi control/communicator and the enclosure are shipped together. The control, however, still needs to be installed into the enclosure. Hardware for mounting the enclosure to a wall, and the control to the enclosure is located in its own hardware pack. CAUTION: 2.1 Install the Enclosure • Use the enclosure as a template and mark the top mounting holes on the mounting surface. • Pre-start the mounting screws for these two holes.
3.0 Control Terminal Wiring WARNING: Before servicing, remove all power including the transformer, battery and phone line. A complete functional test is required after any programming. TYPICAL BURGLAR AND FIRE WIRING Zone Loop + Input Z– Zone Loop + Input L+ Z– Zone Loop + Input or PO2 L+ Z– Aux. Power (—) (terminal 5 or 7) – L+ CAUTION: Incorrect connections may result in damage to the unit. in + System is Power Limited except for battery terminals.
4.0 Hardware Layout Example ARDIS Interface Module R B G Y Keypads #11 - #15 must be connected to the Options Bus. Keypads #1 - #10 must be connected to the Keypad Bus.
5.0 System Worksheet Account Number Information Name Contact Person Address Voice Phone Number Panel Phone Number City, State, Zip Panel Answers Phone Armed Disarmed Equipment Location and Notes AC Voltage VAC Battery Standby Battery Voltage AH VDC Bell Current AUX Current A A Control Panel Transformer Telephone Jack Telephone On Same Line as Panel Earth Ground Connection Alarm Sounder (s) Misc.
5.0 System Worksheet (continued) Personal Identification Number Information Example PIN Information User Pin # Auth. Parti- Name # Level tions 002 PIN Information User Pin # Auth. Parti- Name # Level tions 001 1001 6 1, 2, 4 James L. PIN Information User Pin # Auth. Parti- Name # Level tions PIN Information User Pin # Auth.
5.0 System Worksheet (continued) Zone Location and Notes Example Type * Zone/Output Partition & Location Function # Zone # 1 SZ Zn Funct. 1 Type * Zone/Output Function # * = SZ: Single Zone Input MZ: Multiple Zone Input IO: DS7465 (see section 12.
5.
Note: 6.0 System Overview 6.1 DS7400Xi Description The DS7400Xi Control/Communicator is a fully integrated hardwire/ multiplex security/fire alarm system. - It can support up to 128 input zones, 90 individual users, and multiple output options. - It can be partitioned into as many as eight separate systems, thus allowing individual control and reports for each partition. - Up to 15 keypads may be used to provide user interface with the system, as well as programming access for the installer. 6.1.
tem will arm normally. If the test fails, the system will arm, but will indicate a trouble condition. - The DS7447 keypad will display “Communication Err” after [#] [8] [7] is entered. - This can also be used to perform a bell test on arming. • Perimeter Instant: This is a zone programmed to activate an alarm even during the entry/exit delay period. • Siren on Comm.
- It can be silenced (not reset) by entering a valid [PIN] + [Off]. - The display will indicate a Fire Alarm for this zone on all keypads in every partition. - A fire reset command must be entered after silencing the alarm to re-enable this zone. - If this zone is programmed for trouble and the loop opens, the DS7447 keypad will display “Fire Trouble” for this zone and the keypad sounders will beep once every ten seconds.
• Panic/Duress Output: All outputs, including the three on-board outputs, the Octal Relays, and the Output Functions, support a Panic/Duress function. To assign an output as a Panic/Duress Output, program the first data digit as “*1”. Program data digit two for the appropriate partition(s). This output will follow Duress activations, Keypad Emergency Keys B and C, and Invisible and Silent Zone alarms. It will reset after acknowledged by a user or after the burglary bell time-out expires.
7.13 Report Programming • Commercial Fire Mode: When in Commercial Fire Mode, the control panel will perform some functions (e.g. communications) differently to conform with commercial fire regulations. - See Commercial Fire Mode Programming, program address 0186. • Water Flow Zone Delay: This is the amount of time a water flow zone must be violated before the control panel will initiate an alarm. - The delay is necessary to accommodate normal changes in water pressure.
lence a 24-hour or fire zone. • Low Battery: This report is sent when a low battery condition occurs. • Battery Restoral: This report is sent when a low battery condition restores. • AC Fail: This report is sent when an AC failure condition occurs. This report may be delayed in address 0197. • AC Restoral: This report is sent when an AC failure condition restores.
provide this information to your local telephone company. The REN is useful to determine the quantity of devices that may be connected to your telephone line and still have all of those devices ring when your telephone number is called. In most, but not all areas, the sum of the REN's of all devices connected to one line should not exceed five (5.0). To be certain of the number of devices that you may connect to your line, you may want to contact your local telephone company to determine the max.
8.0 8.1.2 Removing a PIN Operating Guide To disable (remove) a PIN, enter: • A Master code, followed by [#] [0]. • [0] • User number of the PIN to be cancelled, followed by [#] User Number 001 can not be disabled in this manner. 8.1 Personal Identification Numbers 8.1.1 General Information When programming Personal Identification Numbers, it is helpful to know the following terms: 8.1.3 Authority Levels • PIN: Personal Identification Number.
8.2 Arming/Disarming Commands For commands to Arm, Disarm, Bypass or set chime mode, see the front cover of this Reference Guide or consult the DS7400Xi Ver. 3+ Users Guide. 8.3 Changing the Date This chart explains the procedure for changing the date at the keypad. It is recommended that this procedure be performed at a DS7447 keypad. No visual cues will be given from a DS7445 keypad. Steps to Change the Date Command Sequence If Accepted, the Display Reads # 1. Enter the Master Code Programming Mode.
8.5 Changing the Time This chart explains the procedure for changing the time at the keypad. It is recommended that this procedure be performed at a DS7447 keypad. No visual cues will be given from a DS7445 keypad. Steps to Change the Time # 1. Enter the Master Code Programming Mode. Command Sequence If Accepted, the Display Reads [Master Code] + [#] [0] "6 Change Time"* (display will scroll to this) [6] “Enter Day" (1...7) # 2. Enter a 6. [1] through [7] # 3. Enter the day. Sunday # 4.
8.7 Automatic Arming Each partition can be programmed to automatically arm once per day. To inform occupants that the system is about to arm, a pre-arming period will begin 15 minutes before the system arms automatically. The keypad sounders, and any outputs programmed to follow the keypad sounders, will pulse five times every minute. During the last five minutes before arming, these sounders will be on steady. Once per minute the keypad will read, “Arm in nn min./PIN + OFF - extend.
8.8 Turning OFF the System under Duress This chart explains the proper procedure for disarming under Duress. Ask your installer if the Duress feature has been activated. A Duress code is used when someone demands, by threatening your life or well-being, that the system be turned off. When used, the code will both turn off the system and report a silent Duress alarm if connected to a monitoring service.
8.11 Emergency Keypad Alarms Armed Status ® Power Fire Armed Perimeter Status Supervisory Power Bell Silenced Fire Trouble ® 1 2 3 4 5 6 7 8 On On 1 2 3 Off 1 2 3 Off 4 5 6 Perimeter Only 4 5 6 Perimeter Only 7 8 9 No Entry 7 8 9 No Entry * 0 # Bypass * 0 # Bypass System Reset System Reset A B A C B C The Emergency Alarm Keys [A], [B], and [C] may generate Fire, Special Emergency, and Panic Alarms if programmed by the installer.
8.12.3 Installation Considerations Proper location of detection devices is one of the most critical factors in a fire alarm system. The following are some general considerations: Bedroom * Hall Living Room Basement * Dining Room Bedroom Kitchen • Do not install smoke detectors where normal area temperatures are above 100 degrees F (38 degrees C) or below 32 degrees F (0 degrees C).
8.13.3 Communicator Test This test is available only if your system transmits alarms and system information to a monitoring service, and has been programmed by the security installing company to permit communicator tests. A long beep will initially sound to acknowledge the start of the test. If the test is successful, the sounder will again issue one long beep. If the test fails, the keypad sounder will turn ON continuously. To silence the sounder, enter you PIN followed by the [#] key or press the [*] key.
8.13.6 Error Displays This chart explains the procedure for reading Error displays when the green Power Light is flashing on the keypad. Control panel problems are indicated by a flashing green Power Light. The DS7447 display will also read “Control Trouble, Enter #87.” The DS7445 will only flash the green Power Light. The Error displays may only be read when the control is disarmed. Contact your installing company if the problems persist. 1.
9.0 The Master Keypad Your system may include a Master keypad. A Master keypad is a DS7447 keypad programmed to give a user access to all the partitions he has access to, not just the partition the Master keypad is in. This is different from a Standard keypad, in that Standard keypads only give access to the single partition they are in. Commands entered at the Master keypad will affect all the partitions the user has access to.
9.3 Disarming from the Master Keypad Disarming from the Master Keypad Disarming all the Partitions you have access to. Enter your PIN followed by the [Off] key. This will disarm all of your partitions, even if some are already disarmed. You must enter Single Partition Mode to disarm the necessary partitions one at a time. Disarming only some of your Partitions 1. 2. 3. 4. 5. 6. 7. Enter your PIN, followed by the [#] key twice: [1] [2] [3] [4] [#] [#].
• If you wish to read back the value of that address, press the [#] key. • If you wish to program a different address, press the [*] key two times and enter the program address you wish to program. If you make a mistake at any time, press the [*] key two times (before pressing the [#] key). This will clear the display, allowing you to enter the program address you wish to work with. 10.4 HEX values Some Data Digit values will be higher than 9.
If the chart looks like this, only a single feature is available to be programmed for that particular address. Select Option Disabled Perimeter Instant 24-Hour Entry/Exit Delay #1 Entry/Exit Delay #2 Represents the option/feature available for this address. Example: To select Disabled, enter the data digit as a 0. To select Entry/Exit Delay #2, enter the data digit as a 4.
12.0 Programming 12.1 General Control Programmong: Program Address (0000) Example: To program the system-wide General Operating parameters as: allowing Normal and Custom Arming, Operating at 60 Hz., and to Restore when a Zone Restores. General Control programming defines the system-wide general operating parameters. See Glossary (section 7.1) for further details. Data Digit 1 = [2], Data Digit 2 = [1].
12.2 Zone Function Programming: Program Addresses (0001-0015) A Zone Function is the description of how a zone will behave. Up to 15 different Zone Functions may be programmed. Each zone must be assigned a zone function. Multiple zones can be programmed to follow the same zone function. See section 6.3 and 7.2 for further details. Example: To program Zone Function 1 as: Steady Alarm Output, Alarm on Short, Trouble on Open, Interior Instant. Data Digit 1 = [6], Data Digit 2 = [7]. ** = Only when disarmed.
12.3 Zone Programming: Program Addresses (0018-0145) In Zone Programming, each zone is defined according to: • Input (single or multiple zone input, or a DS7465) • Zone Function or Output function (1-15). The DS7465’s relay is the only device that will follow the output functions; its input loop will follow a zone function. All single and multiple zone inputs will follow a zone function. See section 6.2 and 7.3 for further details.
12.5 Zone Bypass Programming: Program Addresses (0016-0017) Example: To program zone functions 1 - 7 so they can not be bypassed and zone function 8 so it can be bypassed. Zone Bypass programming determines which zone functions can be bypassed. Zone functions that can not be bypassed can not be force armed either. Fire zones can never be manually bypassed, but can be force armed. The Default of [0] or [8] means those zones can be bypassed. Data Digit 1 = [*] [5], Data Digit 2 = [7].
12.6 Output Programming: Program Addresses (0146-0148) Output programming defines the event, partition, and type of alarm (burg or fire) that will trigger each of the three physical outputs on the control panel. Example: To program the Programmable Output 1 as: following a Burglar Zone Alarm that is in Partition 1. PA 0147: Data Digit 1 = [6], Data Digit 2 = [1]. PA 0149: Data Digit 1 = [8], Data Digit 2 = [0]. See section 3.0 for the location of the physical outputs on the control panel.
12.8 Partition Control Programming: Program Address (0165) Example: To program the Partition Control as: the System will use 3 Partitions, and Partition 1 is common to Partitions 2 and 3. Partition Control programming defines the number of partitions in use and the common area (common area can only be partition 1). Data Digit 1 = [2], Data Digit 2 = [1]. See Glossary (section 7.5) for further details.
12.10 Keypad Assignment Programming: Program Addresses (0173-0180) Example: To program Keypad 1 as an Alpha Keypad that is assigned to Partition 1. Keypad Assignment Programming is where you assign the keypad type and the partition it belongs to. PA 0173: Data Digit 1 = [1], Data Digit 2 = [0]. PA 0208: Data Digit 1 = [2], Data Digit 2 = [0]. See Glossary (section 7.6) for further details.
12.12 Emergency Key Programming: Program Addresses (0181-0182) Emergency Key and Panic Key programming disables or activates these keys (the A, B, and C keys) located on the keypads. It also determines a silent, pulsed, or steady alarm. Example: To program the Fire Key and the Special Emergency Key as both having a Steady Alarm. Data Digit 1 = [2], Data Digit 2 = [2]. See Glossary (section 7.7) for further details.
PA 0184 Data Digit 12.13 Custom Arming Programming: Program Addresses (0183-0184) (Continued) 1 Select Options Bypass Zone Function 9 Bypass Zone Function 10 Bypass Zone Function 11 Bypass Zone Function 12 2 Enter the Data Digit as a: 0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5 *0 - *5 are Hex values. They will display as A - F at the keypads. Select Options Bypass Zone Function 13 Bypass Zone Function 14 Bypass Zone Function 15 Enter the Data Digit as a: 0 1 2 3 4 5 6 7 12.
12.15 Commercial Fire Mode Programming: Program Address (0186) Example: To program the Commercial Fire Mode parameters as: Central Station Commercial Fire Mode enabled, with a 10 second delay on Waterflow Zones, having the Bell and Aux. activate on Fire Alarms, and using California March Time. This section describes how to define the parameters for the Commercial Fire Mode. Data Digit 1 = [8], Data Digit 2 = [1]. See Glossary (section 7.10) for further details.
12.16 Open/Close Report Control Programming: Program Address (0187) Example: To program to send Open/Close Reports from Partition 1 and to send Trouble Reports on Closings for all Bypassed Zones. See Glossary (section 7.12) for further details. Data Digit 1 = [1], Data Digit 2 = [1].
12.19 Timer Programming: Program Addresses (0191-0196) Example: To program the Entry Delay Time 1 for 60 seconds. Entry and Exit Delay Timers are in 5 second intervals (the maximum delay time is 255 seconds). Data Digit 1 = [1], Data Digit 2 = [2]. Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0] Enter the Program Address: [0] [1] [9] [1] Enter Data Digit 1: [1] Enter Data Digit 2: [2] Enter the pound key: [#] Program the next Address, Program a different Address, or Exit the Programmer’s Mode.
21.21 General Code “Arm Only” Programming: Program Address (0198-0201) This allows for a user with a General Authority level to Arm and Bypass zones he is not able to Disarm. Example: To program a General Authority level to be able to Arm and Bypass zones he is not able to Disarm in Partition 1. See System Overview (section 6.1.3) for further details. Data Digit 1 = [1], Data Digit 2 = [0].
12.23 DS7412 RS232 Interface Control Programming: Program Address (0206) DS7412 RS232 Interface Control Programming allows you to enable or disable the DS7412 and to select which history events are sent to the printer as they occur. Selecting “No Events” will cause the history to be printed only on command. To print the History Buffer starting from the most recent event, enter the Master Code followed by [#] [0] [8]. To stop printing, enter Master Code [#] [0] [8] again.
12.25 Report Programming: Program Addresses (0256-0304 and 0320-0340) • To send the User number along with open, close, or partial close reports: place an ‘F’ (*5) in the extended digit. • To disable a report (meaning: nothing will be sent): place a ‘0’ in the reporting digit. • When using SIA or Contact ID format, place a ‘1’ in the reporting digit of each report you wish to enable. It is not necessary to program the extended digit. • For suggested values for 4/2 and BFSK format, see section 16.1-16.3.
Report Programming (Continued) Default Report Address Default Reporting Extended Digit 1 Digit 2 Report Address Zone Funct. 15 Trouble 0304 00 Remote Program Successful 0330 00 Open 0320 00 Remote Prog. Unsuccessful 0331 00 Close 0321 00 Local Program Successful 0332 00 Duress 0322 00 Local Program Unsuccessful 0333 00 Partial Close 0322 00 System Trouble 0334 00 First Open After Alarm 0324 00 System Trouble Restoral 0335 00 Low Battery 0325 00 Comm. Test/System off Norm.
12.27 Account Code Programming: Program Addresses (0496-0526) Example: To program Partition 1 Phone #1 Account Code to be 2332. Data Digit 1 = [2], Data Digit 2 = [3], Data Digit 3 = [3], Data Digit 4 = [2]. Account Code programming defines the number transmitted to the central station that identifies this panel. It also identifies which partition is reporting from this panel.
12.28 Phone Number General Control Programming: Program Address (0528) Example: To program the parameters to enable the Remote Programmer Call-back feature, to dial Pulse on all Phone Numbers, to send Alarm Reports via either ARDIS or Digital, and to use 110 Baud comm. for WDSRP. See Glossary (section 7.14) for further details. Data Digit 1 = [1], Data Digit 2 = [0].
12.29.1 Compatable Receivers ● = The Format type the DS7400Xi supports and the Digital Alarm Communicator Receiver accepts. SIA Contact ID BFSK 4/2 4/1 3/1 E w/Parity Receiver 3/1 w/Parity Contact your central station regarding which format to use and if a special line card is required. 3/1 Note: 3/1 E (Extended) Format The following table lists those Digital Alarm Communicator Receivers and Formats that are compatible with the DS7400Xi. ADEMCO: Model 685 F.B.I.: Model CP-220 I.T.I.
12.31 Programmers and Master Code Programming: Programming Addresses (0532-0534) Example: To program the Programmer’s Code to be 3 4 4 3. Data Digit 1 = [3], Data Digit 2 = [4], Data Digit 3 = [4], Data Digit 4 = [3].
12.
12.33 Output Function Programming: Program Addresses (1472-1516) Example: To program the Output Function 1 to follow a Zone Burg Alarm. Data Digit 1 = [6], Data Digit 2 = [1], Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0] Enter the Program Address: [1] [4] [7] [2] Enter Data Digit 1: [6] Enter Data Digit 2: [1] Enter the pound key: [#] Program the next Address, Program a different Address, or Exit the Programmer’s Mode.
12.33.
12.35 Call-Out Timer Programming: Program Addresses (1521-1524) Example: To program the Remote Programmer Call-Out hour and minute as 2:30 pm. This section allows you to define the Hour and Minute for the Communicator Test Report and Remote Programmer Call-Out. Hour: Data Digit 1 = [1], Data Digit 2 = [4]. Minute: Data Digit 1 = [3], Data Digit 2 = [0]. The default time for the Communicator Test Report to be sent and for the control to call the Remote Programmer is Midnight.
12.37 Alpha Description Programming: Program Addresses (1526-3701) Alpha Description Programming allows up to 16 characters to be programmed for the description of each partition or zone (e.g. “J. Hill’s Office”). If a description is less than 16 characters, leave the remaining address(es) blank. Once programmed, the descriptions will be displayed on the alpha keypads.
12.37.
12.37.
12.37.
12.37.
12.38 Phone Number Programming: Program Addresses (4028, 4038, 4048) Example: To program Phone Number 1 as 555-1212.
13.0 Installation Guide for U.L. Listed Systems 13.1 DS7400Xi U. L. Listings: • Household Fire Alarm, U. L. Standard UL985 • Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Type Initiating: Automatic, Manual, Sprinkler Supervisory, and Waterflow), U. L. Standard UL864 • Household Burglary Alarm, U. L. Standard UL1023 • Police Station Connection Grades AA and A, U. L. Standard UL365 • Central Station Burglary Alarm Grades AA, A, B, and C; U. L.
• Zones must be connected to U. L. Listed, compatible devices. • 50 Hz. AC input cannot be used in U. L. Listed Requirements. • The ground wire provided with the enclosure must be connected between the “Earth GND” connection on the control and the enclosure tab. • The keypad panic alarm output must follow the corresponding zone function’s programming (e.g. fire = pulsing [or steady if not a combination], burglary = steady). In all cases, the special emergency keys must be silent.
4. Alarm Output Programming: • Program Address 0146 must be programmed as: Data Digit 1=6, Data Digit 2=3. • Program Address 0149 must be programmed as: Data Digit 1=8. NOTE: In a system that includes both fire alarm and burglar alarm devices, the system must produce distinct sounds for fire and burglar alarm conditions either by using different indicating appliances or by using distinct cadences for the same appliance. 13.
B. Grade A Installations using Digital Alarm Communicator Transmitter with local bell Follow General System Requirements as listed in 13.4. Required Accessories: • The control must be the Detection System’s model DS7400XiCC with a cover actuated tamper switch installed. • The Ademco Model AB-12 bell/housing* (see section 13.6). 1. Timer Programming: • Bell Cutoff Times (Program Addresses 0195 and 0196) must be programmed for not less than 15 minutes.
1. Report Programming: • Burglar Zone Reports must be programmed for those zones used. • Fire Zone Reports must be programmed for those zones used. • Low Battery Report (Program Address 0325) must be programmed. • AC Failure Report (Program Address 0327) must be programmed. • Open Report (Program Address 0320) must be programmed. • Close Report (Program Address 0321) must be programmed. • 24-Hour Check-In Reports (Program Addresses 0329 and 0336) must be programmed. 2.
14.0 Report Programming 14.
14.
14.3 Pager Format The Pager format allows the control panel to dial a digital pager and leave a numeric message which includes an account ID and report type. The telephone number is dialed when a report is available. At the completion of the telephone dialing, a fixed time delay equal to 10 seconds occurs. This delay allows time to connect with the pager service, while skipping over any voice announcement. When the delay has ended, the numeric message is sent.
Pager Format (Continued) Reports with Restorals Restoral Report Address Address Value Value Low Battery 0325 6 0 0326 7 0 AC Fail 0327 6 1 0328 7 1 System Trouble 0334 6 2 0335 7 2 Keypad Fire 0256 9 0 0257 9 1 System Test 0339 6 5 0340 7 5 Reports without Restorals Address Value Open 0320 8 0 Close 0321 8 1 Partial Close 0322 8 2 First Open after Alarm Exit Error 0324 0337 8 8 3 6 Recent Closing 0338 7 Keypad Emergency 0273 8 9 Keypad Panic
15.0 Report Programming - Values Sent 15.
15.
15.2 Contact I.
15.2 Contact ID Format (Continued) CID event code CID data field 602 None Communicator test report 601 None Remote programming successful report 412 None Remote programming failure report 413 None Local programming successful report 306 None 306 Restoral None 354 None 354 Restoral None 330 None 330 Restoral None 333 None Multiplex bus restoral 333 Restoral None Radio receiver tamper 137 None 137 Restoral None 300 None Aux.
16.0 Multiplex Zone Addressing Guide • Before installing a multiplex device, its address and other information must be programmed into the control panel. Perform the following: • Program the control panel. - Refer to section 14.3, Zone Programming. This section allows you to define the Multiplex Zone’s address (zone number), its type (single or multiple zone input device, or a DS7465), which zone or output function it will follow (1-15) and its partition (1-8).
17.0 Troubleshooting Guide 17.1 Keypad Problems Symptom Probable Cause Possible Solution Entry Error: Please Re-enter will display on keypad. A three beep error tone will sound continuously. a) Two or more keypads share the same address. a) Install keypad jumper properly in back of keypads. b) The DS7430 or DS7433 is installed in the wrong pins. b) Be sure the DS7430 or DS7433 is installed properly. a) The keypad not addressed properly.
Keypad Problems (Continued) Symptom Chime Mode (#7) does not work when a zone is faulted. Some functions won’t work on a Master keypad. Probable Cause Possible Solution a) Not activating for interior zones. a) Chime mode only activates for perimeter zones Chime mode must be programmed. Also, if the perimeter zone has trouble enabled (trouble on open), the chime won’t work if that zone is opening. b) The keypad is not assigned to the same partition as the zone being activated.
Zone Problems (Continued) Symptom Probable Cause Possible Solution Zones 9 and above show Not Ready, Zone Trouble. a) The multiplex expansion module is not installed properly. a) Make sure the multiplex expansion module is seated properly in the upper pins on the DS7400Xi circuit board. b) Multiplex wiring is missing or not installed properly. b) Check wiring and perform a system reset. c) 8-Input remote module DIP switches are not set properly.
General System Problems (Continued) Symptom Probable Cause #87 display = RAM Fault #89 display = System Fault 01 Possible Solution a) An EEProm fault can be caused by disconnecting power from the control while it is in program mode. In this case, enter then exit program mode to clear. or b) Try to clear the error at the keypad by entering a PIN then Reset. #87 display = ROM Fault #89 display = System Fault 02 c) Remove AC and battery power, then re-apply.
General System Problems (Continued) Symptom #87 display = Ground Fault #89 display = System Fault 04 Probable Cause Possible Solution There is a short to ground somewhere in the system. Disconnect field wiring from each terminal while watching the keypad display. When the keypad power LED stops flashing, you have found the wire that is causing the ground fault. Note: The LED will not stop flashing if there is another system fault present.
General System Problems (Continued) Symptom #87 display = Battery Trouble #87 display = Zone Trouble Probable Cause Possible Solution a) The battery failed a battery test. a) If there has just been a power failure, wait at least two hours for the battery to recharge then perform a System Reset to re-test the battery and clear the error. b) The battery is defective. b) Replace the battery. c) The wiring to the battery is disconnected. c) Check wiring.
18.
Address 0205 0206 0207 0208 0209 0210 0211 0212 0213 0214 0215 0256 0257 0258 0259 0260 0261 0262 0263 0264 0265 0266 0267 0268 0269 0270 0271 0272 0273 0274 0275 0276 0277 0278 0279 0280 0281 0282 0283 0284 0285 0286 0287 0288 0289 0290 0291 0292 0293 0294 0295 0296 0297 0298 0299 0300 0301 0302 0303 0304 0320 Description Arming Warning DS7412 Interface Control DS7412 Interface Config. Keypad Partition Assign. Keypad Partition Assign. Keypad Partition Assign. Keypad Partition Assign.
Address 1466 1467 1468 1469 1470 1471 1472 1475 1478 1481 1484 1487 1490 1493 1496 1499 1502 1505 1508 1511 1514 1520 1521 1523 1525 1526 1542 1558 1574 1590 1606 1622 1638 1654 1670 1686 1702 1718 1734 1750 1766 1782 1798 1814 1830 1846 1862 1878 1894 1910 1926 1942 1958 1974 1990 2006 2022 2038 2054 Description Octal Module #2, Relay #11 Octal Module #2, Relay #12 Octal Module #2, Relay #13 Octal Module #2, Relay #14 Octal Module #2, Relay #15 Octal Module #2, Relay #16 Output Function 1 Output Function
Index Symbols 24-Hour Zone 15 4/2 Format 69 A A/C Fail Report 45 AC Fail Report 19 AC Restoral Report 19 Access Output 16 Access PIN 21 Account Code Programming 50 Ademco AB-12 Bell 68 Alarm on Open 15 Alarm on Short 15 Alarms, Fire 25 Alarms, Invisible 15 Alarms, Silent 15 Alpha Programming 58 Answering Machine Bypass 19 ARDIS 49 Arm Only 46 Arm Only PIN 21 Arming, Custom 1, 14 Arming, Force 1 Arming, Maximum Security 14 Arming, Normal 1, 14 Arming, Perimeter 1, 14 Arming, Perimeter Instant 14 Arming Warn
Master Keypad Programming 17 Master PIN 21 Maximum Security Arming 14 Multiple Keypad Use 18 Multiple Zone Input 16 Multiplex Zone 77 N Normal Arming 14 O Octal Relay 53 ON during Entry Pre-Alert 16 ON for 10 seconds 16 ON when System is Armed 16 Open/Close Report 44 Output, Access 16 Output Cross Matrix 55 Output Function programming 55 Output, Keypad Sounder 16 Output, Panic/Duress 17 Output Partition 38 Output Partition Assignment 56 Output Programming 16 Output programming 38, 55 P Pager Format 71 Pa
PRODUCT UPDATE Detection Systems, Inc. 130 Perinton Parkway Fairport, N.Y. 14450 Service (800) 374-7454 Sales (800) 289-0096 (716) 223-4060 CONCERNS: U.L.C. Commercial Fire Applications AFFECTS: DS7400Xi Control Panel DATED: February 16, 1996 ® DS7400Xi Reference Guide Addendum For DS7400Xi Underwriters Laboratories of Canada (U.L.C.) Commercial Fire Applications, the following two modifications are required: 1.