RXT Wireless Configuration Tool
RXT WCT Instruction Manual Rev 0.0 Page 12 of 33
NOTE: It is recommended that the Network ID be set to the same value as the Channel to
simplify settings.
3.5.2 Operations
The Operations section encompasses three main operations performed for both the RXT-300 and RXT-320.
Search My Network Searches for RXTs in My Network. Results are listed in RXTs in My Network.
Reboot RXT(s) Reboots the radios on RXTs that are selected in RXTs in My Network.
Upload Image Changes the RXT’s image on RXTs selected in RXTs in My Network.
Figure 14 RXT-320 Operations Section
The Search My Network operation starts a search for RXTs based upon the Channel and Network ID currently
set in My Network. The RXT WCT will continue the search while RXTs continue to respond. The RXTs that
are found are listed in the RXTs In My Network section. As the search proceeds, a Cancel button is displayed
and if selected will immediately stop the search.
NOTE: RXTs found indicates there was a response at the time during the search. The search
WILL NOT remove any RXTs from the list, meaning that if an RXT is powered down after the
search was done, the list will NOT be updated. To generate a fresh list of RXTs, the RXTs In
My Network list must be cleared and then the search can be run again to find the current RXTs.
The Reboot RXT(s) operation can be used to resolve issues when RXTs are not operating properly.
The Upload Image operation should only be used when directed by Detcon personnel at the factory and is used
to change the image on the RXT radio.
Four additional operations can be performed for RXT-300s only. These operations are specific to the RXT-
300’s capabilities.
Config Mode Turns the RXT’s configuration mode ON or OFF.
Configure RXT(s) Loads the RXT with the selected configuration file.
Restore NV Defaults Restores the non-volatile memory with default parameters.
Clear RXT Erases the RXT’s current configuration. (Performed by Detcon personnel only)
Figure 15 RXT-300 Operations Section