Alarm Out Events This is a submenu that allows the user to select which RXT-300 events will generate
alarms and which relays will be triggered from the events. There are four events that are
monitored: Network Down, RXT Offline, Battery Fault and Battery Alarm. All four RXT
events default to relay 4 but can be individually assigned to any relay.
Network Down occurs when no Master has been detected for an extended period.
RXT Offline occurs when communication is lost to one or more RXT-300s in the system.
Battery Fault occurs when a battery is attached or detected and then communication is lost
with the battery.
Battery Alarm occurs when the battery life remaining drops below the Low Battery
threshold set previously.
Alarm Out
Properties This is a submenu where the user sets the relay properties for the relay outputs of the
current RXT-300 and can be ignored if the Alarm outputs are unused. It sets the Energize/
Non-Energize, Latching/Non-Latching, Silence-able/Non-Silence-able properties for each
Alarm output.
Advanced This is a submenu of advanced settings that can be adjusted such as Modbus™ timeouts
and retries or network timeouts and retries. These would not be changed normally unless
directed to do so by Detcon personnel.
3.3.3 Device(s) Tab
The Device(s) tab is used to set up devices (sensors) that have been identified to be added to the system. These
settings define the Sensor type, Modbus™ settings and Alarm settings. All sensors are accessed using
Modbus™ protocol including the 4-20mA sensors. Alarm settings include thresholds and mapping of Alarm
events to relay outputs.