Owner's manual

1600A-N4X
1600A-N4X Instruction Manual Rev. 0.2 Page 19 of 38
NOTE: The 1600A Device # is in decimal format, and the serial address switch setting for the 600 or 700
Series Sensor is in hexadecimal format. This means that device number 10 decimal on the 1600A
corresponds to the 600 or 700 Series Sensor at address 0A hexadecimal.
4.1.5 4-20mA Output Setup
This menu entry is used to address Detcon AO-4 modules 4-20mA output.
NOTE: If there are no AO-4 modules being used, do not enter any device and address information on this
screen. Misinformation entered here will cause the controller to generate a ‘No Communication Fault’.
Figure 27 Set-up 4-20mA Outputs
Make sure to set each AO-4 module to a unique module address using the front panel switches. The values
should be as follows:
CH# AO4 Address
01 thru 04 81 Hex
05 thru 08 85 Hex
09 thru 12 89 Hex
13 thru 16 8D Hex