Owner's manual

1600A-N4X
1600A-N4X Instruction Manual Rev. 0.2 Page 18 of 38
Figure 25 Accessing Serial Setup
Figure 26 Serial Setup screen
Addressing Serial Sensors
When connecting to a Detcon Model 600 or Model 700 Series sensor, the addressing procedure is different.
First, note how the gas sensors are addressed. Each sensor must be set to a different address. The addresses
start from 01 and count up to 16 (hex 10). An example is shown below to explain the procedure. To address
the gas sensors, set the following:
CH # Sensor Address CH # Sensor Address
01 01 Hex 09 09 Hex
02 02 Hex 10 0A Hex
03 03 Hex 11 0B Hex
04 04 Hex 12 0C Hex
05 05Hex 13 0D Hex
06 06 Hex 14 0E Hex
07 07 Hex 15 0F Hex
08 08 Hex 16 10 Hex
NOTE: the CH# is the gas channel number displayed on the Main Display. The sensor address is the
serial ID address (in Hexadecimal) set at the 600 or 700 Series sensor.