User Manual

Model 1000 H2S Echem
Model 1000 H2S Echem Instruction Manual Rev. 2.8 Page 21 of 30
Sensor life is an estimated remaining use of the sensor head, between 0% and 100%
Example: 85=85% sensor life
Register # High Byte Low Byte
40001 Detectable Range
i.e. 100 for 0-100 ppm, 50 for 0-50% LEL, etc
Register # High Byte Low Byte
40002 Current Gas Reading
The current gas reading as a whole number: If the reading is displayed as 23.5 on the display, this register
would contain the number 235.
Register # High Byte Low Byte
40003 Alarm 1 Set point
This is the trip point for the first alarm.
Register # High Byte Low Byte
40004 Alarm 2 Set point
This is the trip point for the second alarm.
Register # High Byte Low Byte
40005 Status Bits Status Bits
High Byte
Bit 7 Not used, always 0
Bit 6 Not used, always 0
Bit 5 Not used, always 0
Bit 4 Not used, always 0
Bit 3 1-Unit is in calibration 0-Normal operation
Bit 2 1-Alarm 2 is ascending 0-Alarm 2 is descending
Bit 1 1-Alarm 2 is normally energized 0-Alarm 2 is normally de-energized
Bit 0 1-Alarm 2 is latching 0-Alarm 2 is non-latching
Low Byte
Bit 7 1-Alarm 2 Relay is energized 0-Alarm 2 Relay is not energized
Bit 6 1-Alarm 1 is ascending 0-Alarm 1 is descending
Bit 5 1-Alarm 1 is normally energized 0-Alarm 1 is normally de-energized
Bit 4 1-Alarm 1 is latching 0-Alarm 1 is non-latching
Bit 3 1-Alarm 1 Relay is energized 0-Alarm 1 Relay is not energized
Bit 2 1-Fault is normally energized 0-Fault is normally de-energized
Bit 1 1-Fault is latching 0-Fault is non-latching
Bit 0 1-Fault Relay is energized 0-Fault Relay is not energized
The following is a typical Master Query for device # 8:
Field Name HEX DEC RTU
Slave Address 08 8 0000 1000
Function 03 3 0000 0011
Start Address Hi 00 0 0000 0000