Owner's manual

13-73
EQP LOGIC EDITOR
Version 6.0
Item 43 - Oi Mode
Optical Integrity mode can be selected with this variable.
Oi Mode
Value
Denition
0
Automatic
1
Manual
Item 44 - Latching
0 = non-latching output.
1 = latching output.
Item 45 - ARM Output Mode
See the ARM section for a description of this variable.
Item 46 - Activation Time
The output hold on time can be set with this variable.
Item 47 - IR Sensitivity
The IR for UVIR flame detectors always uses 0.125 second gate length for sampling the counter. The signal is
compared to the threshold 0.5 second.
IR Sensitivity
Value Denition UV/IR X3301
Counts per gate Effective counts per second
1 Low 8 64 Low (not used)
2 Medium (default) 6 48 Medium
3 High 4 32 High (not used)
4 Very High 2 16 Very High (Default)
Item 48 - IR Oi Threshold
The Oi test will run for a maximum of five seconds.
IR Oi Threshold
Value
Denition Counts per Second
1
Low 64
2
Medium (Default) 48
3
High 32
4
Very High 16
DEVICE ITEM NUMBER DESCRIPTIONS