Owner's manual
13-72
EQP LOGIC EDITOR
Version 6.0
DEVICE ITEM NUMBER DESCRIPTIONS
Item 38 - Input Static Logic Mode
Input mode is used to determine if static logic should activate controller alarms on input activation. For example,
if mode 1 is selected, static logic will activate the controller fire alarm when the input is activated.
Mode Denition
0
Invalid
1
Fire Alarm
2
Trouble
3
Low Gas Alarm
4
High Gas Alarm
5
Supervisory
6
Other
Item 39 - UV Sensitivity
Sensitivity
Value
Denition Standard Mode Star Mode
1
Low 96 cps 96 cups
2
Medium (Default) 48 cps 48 cps
3
High 24 cps 24 cps
4
Very High 8 cps 8/16 cps
Item 40 - Time Delay
Valid times are from 0 to 7 seconds with a default value of 5 seconds. This item is typically used to adjust the
amount of time a fire must persist before it is deemed to be an actual fire.
Item 41 - UV Arc Rejection
UV Arc Rejection
Value
Denition Gate Length
1
Low 0.250
2
Medium (Default) 0.125
3
High 0.0625
4
Very High 0.0625
Item 42 - UV Processing Mode
UV processing mode can be selected with this variable.
UV Processing Mode
Value
Denition
0
Standard
1
STAR
DEVICE ITEM NUMBER DESCRIPTIONS