Owner manual

14 95-85624.1
APPENDIX F
PSS-MP TEST LAMP
Figure F1—PSS-MP Test Lamp
LAMP REPLACEMENT
REPLACE XENON LAMP MODULE WITH PN 18801 (UNDERWATER KINETICS).
WARNING
THIS UNIT IS NOT RATED FOR USE IN HAZARDOUS (CLASSIFIED) LOCATIONS.
CAUTION
A FULL SYSTEM TEST RESULTS IN AN ALARM OUTPUT. THIS WILL RESULT IN THE
AUTOMATIC SUPPRESSION SYSTEM BEING ACTIVATED IF IT IS NOT DISABLED PRIOR
TO TESTING.
OPERATION
TURN ON PSS-MP, WAIT 15 SECONDS. TO CAUSE AN ALARM, HOLD PSS-MP SO THAT
THE INFRARED FILTER LENS IS LESS THAN 1 INCH FROM THE FRONT OF THE FLAME
DETECTOR TO BE TESTED. IT CAN TAKE SEVERAL SECONDS FOR THE DETECTOR TO
ALARM.
NOTE
FOR VALID TEST RESULTS, THE TEST LAMP AND THE SENSOR UNDER TEST MUST BE
AT APPROXIMATELY THE SAME TEMPERATURE.
BATTERY REPLACEMENT
THE TEST LAMP REQUIRES 6 ALKALINE C-SIZE BATTERIES.
WARNING
CHANGE BATTERY IN NON-HAZARDOUS LOCATION ONLY.
ON
OFF
INFRARED BEAM
INFRARED FILTER LENS
8 5/8
2 3/8
+
+
+
+
+
+
C
CCC
CC