Owner manual
13 95-85624.1
PM-5MPX
PM-5MPX
PM-5MPX
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
+24 VDC
+24 VDC
DC RETURN
DC RETURN
ALARM +
ALARM –
ALARM –
ALARM +
CONTROL ROOM
INSTRUMENTATION
HAZARDOUS LOCATION:
CLASS I, DIV. 2, GROUPS A, B, C & D.
CLASS II, DIV. 2, GROUPS F & G.
CLASS III, DIV 1 & 2.
NON-HAZARDOUS LOCATION
NOTES: 1. FOR INSTALLATION IN NONINCENDIVE,
CLASS I, DIVISION 2, GROUPS A, B, C &
D; CLASS II, DIVISION 2, GROUPS F & G;
CLASS III, DIVISION 2 HAZARDOUS
(CLASSIFIED) LOCATIONS, OR NON-
HAZARDOUS LOCATIONS ONLY. WIRING
METHODS SHALL BE INSTALLED IN
ACCORDANCE WITH ANSI/NFPA
70 (NEC) ARTICLE 501-4(b) AND
ANSI/NFPA 72.
2. THIS DRAWING SHOWS THREE
SENSORS CONNECTED IN ONE ZONE
IN A CLASS A, STYLE D
CONFIGURATION PER NFPA 72.
ADDITIONAL SENSORS CAN BE ADDED
BY REPEATING THE WIRING PATTERN
OF THE CENTRAL SENSOR.
3. PM-5MPX INTERCONNECTS VIA FLYING
LEAD.
4. ELECTRICAL REQUIREMENT: 9 TO 30
VDC AND 10 MILLIAMPS (MAX) PER
SENSOR.
5. THE OUTGOING AND RETURN
(REDUNDANT) CIRCUIT CONDUCTORS
SHALL NOT BE RUN IN THE SAME
CABLE ASSEMBLY, ENCLOSURE, OR
RACEWAY PER NFPA 72.
PM-5MPX
ELECTRICAL INTERFACE
Wire Color Signal
Red V+, Input Power
Orange V+, Input Power
Black Power Return
Brown Power Return
Yellow Alarm +
Green Alarm +
Blue Alarm –
Violet Alarm –
Gray Trouble +
White Trouble –
Figure E1—Non-Incendive Class A, Style D Wiring (Drawing No. 420034)
APPENDIX E
NON-INCENDIVE
CLASS A, STYLE D WIRING
Hazardous (Classied) Locations:
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 2
Non-hazardous (Non-classied) Locations