Owner manual

8 95-85624.1
APPENDIX A
FM APPROVAL DESCRIPTION AND PERFORMANCE REPORT
HAZARDOUS LOCATION RATINGS
Intrinsically safe for Class I, II, III, Div. 1, Groups C, D, E, F and G Hazardous (Classified) Locations per FM 3610.
Non-incendive for Class I, Div. 2, Groups A, B, C and D Hazardous (Classified) Locations per FM 3611.
AUTOMATIC FIRE ALARM SIGNALING PERFORMANCE (FM 3620: 2000)
RESPONSE CHARACTERISTICS
(Typical Response Time < 0.5 Sec.)
Fuel Size
Distance
(feet)
n-Heptane 1 x 1 foot 18
Isopropanol 8 in. dia. 8
Polypropylene 8 in. dia. 8
NOTE: Response time measurements based upon
shuttered test method.
FALSE ALARM IMMUNITY
False Alarm Source
Distance
(inches)
Modulated Response
Unmodulated
Response
Arc welding, Type E6012 rod, 1/8” dia., 1/4” plate 42 No alarm No alarm
70 W sodium vapor lamp 6 No alarm No alarm
250 W mercury vapor lamp 12 No alarm No alarm
300 W incandescent lamp 8 No alarm No alarm
500 W quartz halogen lamp shielded w/window 30 No alarm No alarm
1500 W electric quartz heater 108 No alarm No alarm
Two 34 W fluorescent lamps <3 No alarm No alarm