User Manual

8
APPENDIX A
Control Drawing Configuration
Figure A1—Control Drawing Configuration (Drawing No. 420031)
PM-5MP & PM-5MP+ CONTROL DRAWING CONFIGURATION
HAZARDOUS (CLASSIFIED) NFPA 72 INITIATING INSTALLATION TYPE CONTROL
LOCATION DEVICE CIRCUIT DWG NO.
CLASS & STYLE
CLASS I, DIV. 1, GROUPS C & D CLASS B, STYLE B INTRINSICALLY SAFE 420032
CLASS II, DIV. 1, GROUPS E, F & G CLASS B, STYLE B INTRINSICALLY SAFE 420032
CLASS I, DIV. 2, GROUPS A, B, C & D CLASS B, STYLE B INTRINSICALLY SAFE 420032
CLASS II, DIV. 2, GROUPS F & G CLASS B, STYLE B INTRINSICALLY SAFE 420032
CLASS III, DIV. 2 CLASS B, STYLE B INTRINSICALLY SAFE 420032
CLASS I, DIV. 2, GROUPS A, B, C & D CLASS B, STYLE B NON-INCENDIVE 420033
CLASS II, DIV. 2, GROUPS F & G CLASS B, STYLE B NON-INCENDIVE 420033
CLASS III, DIV. 2 CLASS B, STYLE B NON-INCENDIVE 420033
NON-HAZARDOUS (UNCLASSIFIED) CLASS B, STYLE B NON-INCENDIVE 420033
CLASS I, DIV. 2, GROUPS A, B, C & D CLASS A, STYLE D NON-INCENDIVE 420034
CLASS II, DIV. 2, GROUPS F & G CLASS A, STYLE D NON-INCENDIVE 420034
CLASS III, DIV. 2 CLASS A, STYLE D NON-INCENDIVE 420034
NON-HAZARDOUS (UNCLASSIFIED) CLASS A, STYLE D NON-INCENDIVE 420034