Device Conguration (Read/Write)
This area of memory holds field adjustable parameters for the device. The Hart configuration changed bit will be set
on writes to this area.
Eclipse Device Conguration
Description Address Value
Modbus Polling Address 40101 1..247
Baud Rate Code 40102 See Codes
Parity Code 40103 See Codes
Gas Type 40104 See Codes
Calibration Gas Type 40105 See Codes
Calibration Method 40106 See Codes
Calibration Cuvette Length
(1.0 to 150.0 mm)
40107 Float LSW
40108 Float MSW
Analog Fault Code 40109 See Codes
4 to 20 Range
(0 to 2%/vol)
40110 Float LSW
40111 Float MSW
Cal Gas Concentration
(1%/vol)
40112 Float LSW
40113 Float MSW
Warmup Fault Level
(0.0 to 24.0 mA)
40114 Float LSW
40115 Float MSW
Blocked Optics Fault Level
(0.0 to 24.0 mA)
40116 Float LSW
40117 Float MSW
Calibration Current Level
(0.0 to 24.0 mA)
40118 Float LSW
40119 Float MSW
General Fault Current Level
(0.0 to 24.0 mA)
40120 Float LSW
40121 Float MSW
Volume in %/vol
(Special Gas Type)
40122 Float LSW
40123 Float MSW
Low Alarm Level
(5 to 50% of scale)
40134 Float LSW
40135 Float MSW
High Alarm Level
(10 to 60% of scale)
40136 Float LSW
40137 Float MSW
Low Alarm Latch 40138 See Codes
High Alarm Latch 40139 See Codes
Reserved 40140
NOTE
Refer to Alarm Relays” in the
Specications section of this manual for
important information regarding alarm
relays.