Manual

B-1 95-86762.1
AppenDix b
ATEX / CE APPROVAL
The following items, functions and options describe the ATEX approval.
APPROVAL
PointWatch Eclipse
®
Infrared Carbon Dioxide Gas Detector, Model PIRECL Series.
0539
®
II 2 G
Ex de IIC T4-T5 Gb
– OR –
Ex de [ib] IIC T4-T5 Gb
(with HART communication port)
DEMKO 01 ATEX 129485X.
T5 (Tamb –50°C to +40°C)
T4 (Tamb –50°C to +75°C)
IP66/IP67.
– OR –
0539
®
II 2 G
Ex d IIC T4-T5 Gb
– OR –
Ex d [ib] IIC T4-T5 Gb
(with HART communication port)
DEMKO 01 ATEX 129485X.
T5 (Tamb –55°C to +40°C)
T4 (Tamb –55°C to +75°C)
IP66/IP67.
HART Communication Port:
Uo = 4.0V Co = 20μF
Io = 100mA Lo = 500μH