Manual

10 95-86762.1
24 VDC
+
+
24 VDC
24 VDC
24 VDC +
24 VDC +
CALIBRATE
+ 4-20 MA
– 4-20 MA
RS-485 A
RS-485 B
RELAY POWER
FAULT
LOW ALARM
HIGH ALARM
1
2
3
4
5
6
7
8
9
10
11
12
13
NO USER CONNECTION
4 to 20 MA
B2051
*
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.
Figure 8—Eclipse Detector Wired for Non-Isolated
4-20 mA Current Output (Sourcing)
24 VDC
+
+
24 VDC –
24 VDC –
24 VDC +
24 VDC +
CALIBRATE
+ 4-20 MA
– 4-20 MA
RS-485 A
RS-485 B
RELAY POWER
FAULT
LOW ALARM
HIGH ALARM
1
2
3
4
5
6
7
8
9
10
11
12
13
NO USER CONNECTION
4 to 20 MA
B2050
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.
*
Figure 7—Eclipse Detector Wired for Non-Isolated
4-20 mA Current Output (Sinking)
24 VDC
+
24 VDC
+
24 VDC
24 VDC
24 VDC +
24 VDC +
CALIBRATE
+ 4-20 MA
– 4-20 MA
RS-485 A
RS-485 B
RELAY POWER
FAULT
LOW ALARM
HIGH ALARM
1
2
3
4
5
6
7
8
9
10
11
12
13
NO USER CONNECTION
+
4 to 20 MA
B2053
*
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.
Figure 10—Eclipse Detector Wired for Isolated
4-20 mA Current Output (Sourcing)
24 VDC
+
24 VDC
+
24 VDC
24 VDC
24 VDC +
24 VDC +
CALIBRATE
+ 4-20 MA
– 4-20 MA
RS-485 A
RS-485 B
RELAY POWER
FAULT
LOW ALARM
HIGH ALARM
1
2
3
4
5
6
7
8
9
10
11
12
13
NO USER CONNECTION
+
4 to 20 MA
B2052
*
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.
Figure 9—Eclipse Detector Wired for Isolated
4-20 mA Current Output (Sinking)