Manual

7 95-8556
10.1
ACCURACY—
Refer to the appropriate Appendix for details.
NOTE
Misalignment will cause the manufacturer stated
Accuracy limits to increase, but remain within the
limits of EN 50241-1, -2, EN 60079-29-4, and IEC
60079-29-4.
TEMPERATURE RANGE—
Operating: 55°C to +60°C (–67°F to +140°F)
Storage: 55°C to +85°C (–67°F to +185°F)
Hazardous Locations: Refer to the appropriate
Appendix for correct ambient
temperature range:
Appendix
A - FM
Appendix
B - CSA
Appendix
C - ATEX
Appendix
D - IEC
HUMIDITY—
5 to 99% relative humidity; designed for outdoor
applications.
OPERATING PRESSURE—
91.5 - 105.5 kPA non-compensated.
MEASUREMENT RANGE—
0-5 LFL-meters.
INTERFERENCE RESISTANCE—
Immune to sun and flare radiation, tested to 800 ±50
W/m
2
≥ 3° to optical axis and common contaminants.
SELF-DIAGNOSTIC TEST—
Fail-Safe operation ensured by performing all critical
tests once per second.
MODULE HOUSING MATERIAL—
316 stainless steel (CF8M).
CONDUIT ENTRY OPTIONS—
Two entries, 3/4 inch NPT or 25 mm.
HART COMMUNICATION PORT—
An intrinsically safe port is provided on the receiver for
connecting a Rosemount/Emerson HART Communicator.
•Maximum separation distance between receiver and
communicator is 610 meters.
OPTICS PROTECTION—
Stainless steel brow provides a degree of protection
against windblown dirt and rain. Heated optics mitigate
against ice and dew formation.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG shielded wire, and are DIN/VDE rated for 2.5
mm
2
wire. Screw terminal required torque range is 3.5–
4.4 lb.-in. (0.4-0.5 N·m). Receiver can be wired using 3
or 4 wires. Transmitter requires two wires (power only).
CERTIFICATION—
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - Other Approvals
FM
APPROVED
®