Manual

95-8556
10.1
Appendix d
IECEx APPROVAL DESCRIPTION
The following items, functions and options describe the IECEx approval.
APPROVAL
Open Path Eclipse Infrared Hydrocarbon Gas Detector, Model OPECL Series.
Receiver Transmitter
IECEx ULD 05.0001X IECEx ULD 05.0001X
Ex d [ib] IIC T5 Gb Ex d IIC T5 Gb
T5 (T
amb
–55°C to +60°C) T5 (T
amb
–55°C to +60°C)
--OR-- --OR--
Ex d e [ib] IIC T5 Gb. Ex d e IIC T5 Gb.
T5 (T
amb
–50°C to +60°C) T5 (T
amb
–50°C to +60°C)
IP66/IP67. IP66/IP67.
HART Communication Port:
U
o
= 4.0V C
o
= 20µF
I
o
= 100mA L
o
= 500µH
U
m
= 250V
IEC Standards:
IEC 60079-0: 2007
IEC 60079-1: 2007
IEC 60079-7: 2006
IEC 60079-11: 2006
IEC 60529, 2.1 ed.+Corr.1:2003+2:2007
IEC 61000-4-3: 2006
IEC Conditions of Certication (general):
• The ambient temperature range is limited to –50°C to +60°C for the Ex d e
[ib]
IIC T5, Ex d e IIC T5 version, and
–55°C to +60°C for the Ex d
[ib]
IIC T5, Ex d IIC T5 version.
• Only suitable certified Ex d or Ex e (as applicable) cable entries and blanking elements are to be used.
• The Model OPECL assemblies are to be installed in places where there is a low risk of mechanical damage.
• The field wiring terminal connections are certified for a single wire in size from 0.2 to 2.5 mm
2
, (or two conductors
with same cross section 0.2 to 0.75 mm
2
). The screws must be tightened down with a torque 0.4 to 0.5 Nm.
• The metal housing of the Model OPECL Gas Detector must be electrically connected to earth ground.
D-1