Output
4 to 20 Milliamperes (Standard)
Relay (Optional)
•Optionincludesasetoffourrelays:
High Alarm
Low Alarm
Auxiliary Alarm
Fault
•Includes4to20maoutput.
Description
•Thelinear4to20maoutput:
corresponds to the field-programmed gas range.
can be calibrated in the field for maximum accuracy.
is user selectable for isolated or non-isolated use.
Refer to the “Setup ” section for programming information.
•The High, Low and Auxiliary Alarm relays are
programmable as a group for either normally energized
or normally de-energized operation.
•HighAlarmrelayisalwayssetforlatchingoperation.
•LowAlarmandAuxiliaryAlarmrelaysareprogrammable
as a group for either latching or non-latching operation.
•Faultrelay is normally energized with nofaults. Faults
are generally non-latching, but faults that occur during
calibration and warmup must be reset.
•LatchingrelaysareresetusingeithertheCalmagnetor
an external reset switch (field installed, user supplied).