SAFETY MANUAL User guide

CERTIFICATION AND FAILURE RATE DATA
All Safety-Certified GT3000 Toxic Gas Detectors are
certified compliant to:
IEC61508: 2010
Type B Element
Systematic Capability: SIL 2 certified
HF T: 0
Low Demand Mode
PFDavg should be calculated for any safety instrumented
function using the GT3000. (Refer to FMEDA report for
necessary information, including DU rate.)
Safety Accuracy: ±10% of applied gas
concentration.
Safety Response Time: Depends on sensor module
being used. Refer to GT3000
instruction manual for details.
Product Life: 3-5 years, based on
manufacturer data.
All failure rate data for SIL verification is in the FMEDA
report, which is available upon request.
ADDITIONAL CERTIFICATIONS
FM, CSA, ATEX, IECEx, CE, and others.
Refer to the GT3000 Instruction Manual for details.
For complete information regarding performance,
installation, operation, maintenance and specifications
of the GT3000, refer to instruction manual 95-8616.
TERMS AND DEFINITIONS
AMS Asset Management System
FMEDA Failure Mode Effects and Diagnostics
Analysis
HART Highway Addressable Remote
Transducer
HFT Hardware Fault Tolerance
LFL Lower Flammable Limit
V/V Percent by volume
PFD Probability of Failure on Demand
(Probability of Dangerous Failure)
PFDavg Average Probability of Failure on
Demand
SFF Safe Failure Fraction
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
GT3000 Electrochemical Toxic Gas Sensor
(consists of one GTX Transmitter and
one GTS Sensor Module)
Detector Electronics Corporation
6901 West 110th Street • Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491 Fax (952) 829-8750
http://www.det-tronics.comE-mail: det-tronics@det-tronics.com
Specications subject to change without notice.
Det-Tronics, the DET-TRONICS logo, and FlexVu are registered trademarks
or trademarks of Detector Electronics Corporation in the United States,
other countries, or both. Other company, product, or service names may be
trademarks or service marks of others.
©Copyright Detector Electronics Corporation 2012. All rights reserved.
R
E
G
I
S
T
E
R
E
D
B
Y
U
L
A
N
D
B
S
I
N
O
.
A
2
3
0
5
N
O
.
2
5
8
2
6
ISO 9001
R
E
G
I
S
T
E
R
E
D
F
I
R
M
R
E
G
I
S
T
E
R
E
D
F
I
R
M
Failure Category
l
sd
l
su
2
l
dd
l
du
SFF
3
GT3000 Analog Output with H
2
S Sensors
0 199 3136 275 92.4%
GT3000 Analog Output with
O
2
Sensor
0 243 3123 141 96.0%
IEC 61508 Failure Rates in FIT
1
1
FIT = 1 Failure / 10
9
Hours
2
It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.
3