SAFETY MANUAL

5.1 95-859917
Certied for use up to SIL 2 Conguration 1oo1D
Architecture Type B Hardware Fault Tolerance 0
Safe Failure Fraction > 90%
Failure Rate Data
Part Model
l
DU
(dangerous undetected failure rate per 10
9
hours)
SFF %
EQP Safety Controller EQ3xxx 87.5 96.7
EDIO Safety Module -
Congured as Input*
EQ3730EDIO
Common = 20.9
Input Monitored for Opens = 6.6
Input Monitored for Opens & Shorts = 0.68
97.1
93.0
99.0
EDIO Safety Module -
Congured as Output*
EQ3730EDIO
Common = 20.9
Output Monitored for Opens, Opens & Shorts = 0.92
97.1
98.9
AIM Safety Module EQ3710AIM
Common = 12
Per Input Channel = 5.16
98.1
93.0
X3301 IR Flame Detector X3301 133 96.3
Eclipse IR Gas Detector
Model PIRECL
132 95.5
EQP Safety Communications 22.8 N/A
* “Common are components common to both inputs and outputs. For lDU calculation:
Example 1: Input and output on same EDIO
lDU = Common + Input + Output
lDU = 20.9 + 0.68 + 0.92 = 22.5
Example 2: Input and output on different EDIOs
lDU = lDU EDIO #1 +lDU EDIO #2
= (Common + Input) + (Common + Output)
= (20.9 + 0.68) + (20.9 + 0.92) = 43.4
Product Life EQ3xxx (Controller): 10-25 years, based on manufacturer data.
Product Life EQ3730EDIO: 6-29 years, based on manufacturer data.
Product Life EQ3710AIM: 6-29 years, based on manufacturer data.
Product Life X3301: 12-27 years, based on manufacturer data.
ProductLifePIRECL:5-40years,basedonmanufacturerdata.
All failure rate data for SIL verification is in the FMEDA report, which is available upon request.
IEC 61508 Failure Rates