SAFETY MANUAL

5.1 95-859916
APPENDIX A
SUMMARY OF SAFETY RELATED DATA
CERTIFICATION AND FAILURE RATE DATA
All Safety-Certified EQP devices are certified compliant to:
IEC 61508: 2000
Type B Device
Systematic Capability: SIL 2 certified
HFT:0
Low Demand Mode
PFDavg should be calculated for any safety instrumented function using the EQP System.
(Refer to tables and / or FMEDA report for necessary information, including DU rate).
Safety Accuracy: Specified per device
Safety Response Time: See ‘System Response Time’ section