Manual
14.1 3-18 95-8533
address. Software selectable baud rates are
9600,19200, 38400, 57600, 115200 and 230400.
Software selectable parity is None, Odd, and Even.
The controller uses 8 data bits with 1 stop bit.
Port Pinout (3-position terminal block)
60 — A
61 — B
62 — GND
Jumper P28 – RS-485 Termination Jumper
1-2 Terminated 121 ohms (factory setting)
2-3 Unterminated
Transceiver input impedance: 68 kohm
Jumper P29 – RS-485 Ground Fault Monitor
1-2 Enabled
2-3 Disabled (factory setting)
1
P25
3
1
60616467 6263656668
P26
3
P27
1
3
RS-232 Receive LED (Green)
RS-232 Receive LED (Green)
RS-485 Transmit LED (Amber)
RS-485 Transmit LED (Amber)
RS-485 Termination Jumper
P28: RS-485 Termination Jumper
P29: RS-485 Ground Fault
MonitorJumper
A B
Channel
Indicators
RS-485 Receive LED (Green)
RS-485 Receive LED (Green)
RS-232 Transmit LED
(Amber)
RS-232 Transmit LED (Amber)
LON COM 2
Termination Jumper
LON COM 1
Termination Jumper
P28
1
3
P29
1
3
P12
PORT 4
P11
PORT 3
P10
PORT 2
P
O
R
T
1
EAGLE QUANTUM PREMIER
Safety System Controller
Fire Alarm
Inhibit
Powe r
SuprHigh Gas
Trouble
Cntrl Flt
Lon FaultLow Gas Ack Silence
Out Inhibit
Eagle Quantum Premier
Time & Date
Cancel Enter Next Previous Reset Acknowledge Silence
DET-TRONICS
®
Figure 3-12—Location of Termination Jumpers, Communication Indicator LEDs and Communication Ports