APPENDIX B
CSA INtErNAtIoNAl CErtIfICAtIoN DESCrIPtIoN
hazardous locations
•RefertoFiguresB-1andB-2forSystemClassificationdetails.
•EQxxxxEMversionsratedClassI,Div.2,GroupsA,B,C,D(T4A).
gas detection
•Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheresper CSA C22.2 No. 152.
Accuracy: ±3% LFL from0to 50%LFL, ±5% LFL from51%to 100%LFL. For the Model PIRECL, referto the
PIRECLmanual(formnumber95-8526)forfurtherCSAgasperformancedetails.
NOTE:
Detector Electronics combustible gas detection K factors are not CSA veried.
•CalibrationofthedeviceshasbeenCSAverifiedusingtherespectiveEQ22xxDCU,EQ22xxDCUEXandPIRECL
SerieswiththeDet-Tronics225130-001(50%LFLmethane)and227115-001H2SCalibrationKits.
•TheEQ22xxDCUSeriescanbeusedwithanyCSACertified4-20madevice.
NOTE
CSA Certication of the 4-20 ma input does not include or imply approval of the gas detection apparatus such
as sensors, transmitters, or devices connected to the system. In order to maintain CSA Certication of the
system, all 4-20 ma gas detection instruments connected to the input must also be CSA Certied.
NOTE
CSA Certication allows the presence and operation of serial communications software in the Controller
(MODBUS, Allen Bradley protocols, etc.); however, the communications functions are not included in the
Certication.