EQPSS SUPERVISING SYSTEM
•NationalFireAlarmCodeperformanceverifiedperANSI/NFPA72-2002.RefertoFiguresA-2andB-2forEQPSS
SupervisingSystemarchitecture.
•Det-TronicsonlytointegrateproprietaryEQPSSSupervisingSystemperDet-TronicsProcedures5072and5073.
EQP SYSTEM MODEL 000523-009 & 000523-010
•TheSystemconsistsof:
 1xEQP2120PS-BPowerSupply,primary; 1xEQ3XXXController(000523-009)
 2xEQP2410PS-PConverter,secondary; 0xEQ3XXXController(000523-010)
 2xQUINT–DIODE/40Redundancymodule; 0xEQ3710AIMModule&1xEQ3730EDIOModule(000523-009)
 1xEQ2220GFMGroundFaultMonitor 2xEQ3710AIMModules&2xEQ3730EDIOModules(000523-010)
•The System is mounted within 60H x 36W x 16D Stainless Steel (type 316), NRTL labeled NEMA 4X rated
enclosure.Theenclosureshallbelockablebykeylockorpadlock.
•EQPsystemmodels000523-009&000523-010aresuitableforClI,Div.2,GRPSA,B,C&D(T4);ClI,Zone2,
GRPIIC(T4)Hazardous(Classified)Locations;Tamb=–20°Cto+49°C.
•Modifications to enclosure(such as conduit entry holes, windows etc.) are permitted when implemented by the
manufactureroftheenclosure.