Instruction Manual

4.2
95-8654
3
Class X is intended for use in a multi-zone system and
requires that the first isolator on each leg be installed
next to the ASH Module, within the same enclosure. In
addition, an isolator is needed between each zone as
illustrated in Figure 4. Alarm receipt capabilities in the
other zones shall be maintained during a single open,
single ground, wire-to-wire short, or open and ground.
Note
The isolator has an operating temperature range
of +32°F to +100°F (0°C to +38°C). This means
that, for Class X installations, the enclosure
temperature will be rated to +100°F (+38°C) max.
Reference Table 1 for further details on the performance
requirements for SCLs as defined by NFPA 72.
LED INDICATORS
LEDs on the front of the ASH Module are provided for
indicating device status conditions. There are 6 LED
status indicators (Power, ASH Module Fault, Loop Fault,
Loop Device Fault, Ground Fault, and Alarm) located
on the front panel (Figure 5). Refer to Table 2 for a
description of the LED indicators.
MOUNTING
The ASH Module can be DIN Rail or Panel mounted.
ADDRESSABLE LOOP DEVICES
See Table 3 for a list of all supported Apollo loop devices.
NOTE
The input and/or output circuits for the Mini
Monitor Module and Priority Mini Switch
Monitor (P/N 55000-765*), Priority Switch
Monitor (P/N 55000-806), Input / Output
Module (P/N 55000-820) and Sound Control
Module (P/N 55000-825) must be no longer
than 20 ft (6 m) and must be installed in conduit
or equivalently protected against mechanical
injury.
For additional information and documentation regarding
all Apollo devices, visit www.apollo-fire.co.uk.
A2591
ASH MODULE
NODE 64
NODE 1
...NODE 63
NODE 3...
NODE 2
ZONE 2
ZONE 1 ZONE 3
.............
.................
.......
........
ASH MODULE APOLLO LOOP
2-WAY COMMUNICATION
.....................
.................
.....................
ISOLATOR ISOLATOR
ISOLATORISOLATOR
ENCLOSURE
Figure 4—Class X Pathway (multi-zone with isolators)
Figure 5—Location of LED Indicators
STATUS
INDICATOR
LEDs
LED Label ASH Module Status*
Green PWR On when power is present
Yellow ASH MOD Fault in the ASH Module
Yellow LOOP Loop Fault
Yellow LOOP DEV Fault with a device on the loop
Yellow GND FLT Ground fault on the Apollo loop
Red ALARM An alarm is present
*Reference to “loop” refers to the ASH Module or Apollo device loops.
Table 2—ASH Module Device Status Indicators
Table 1—Performance of Signal Line Circuits (SLCs)
NFPA 72-2010 Class
Class B Class A Class X
Alarm Trouble ARC Alarm Trouble ARC Alarm Trouble ARC
Condition 1 2 3 4 5 6 7 8 9
Single open X X R X R
Single ground X R X R X R
Wire-to-wire short X X X R
Open and ground X X R X R
ARC = Alarm Receipt Capability
R = Required capability
X = Indication required at protected premises