DET-TRONICS ® INSTRUCTIONS Eagle 2000™ Hazard Event Monitoring System 7/99 Form 95-8424-02
SERVICE MEMO Precautions for Handling Electrostatic Sensitive Devices With the trend toward increasingly widespread use of microprocessors and a wide variety of other electrostatic sensitive semiconductor devices, the need for careful handling of equipment containing these devices deserves more attention than it has received in the past. * Electrostatic damage can occur in several ways. The most familiar is by physical contact.
Table of Contents SECTION I SYSTEM OVERVIEW APPLICATION .........................................................................1 FEATURES .. ...........................................................................1 SYSTEM DESCRIPTION ........................................................1 Detector ...........................................................................1 Communication Gateway – EA2100CG ...........................2 Communication Module – EA2300CM .............................
SECTION VIII SYSTEM STARTUP Figure 12 Basic Eagle System with One Gateway ...........13 Figure 13 Expanded System with Two Network Extenders .........................................................14 Figure 14 Eagle System with Two Gateways ...................14 STARTUP PROCEDURE ......................................................28 Figure 15 Recommended Grounding for Cable Shields ....17 SYSTEM CONFIGURATION ................................................
DET-TRONICS INSTRUCTIONS ® EAGLE 2000™ Hazard Event Monitoring System Section I System Overview NOTE This manual covers the basic operation of the communication module, digital communication unit, gateway, network extender and relay module. It will not cover any specific detector, host device or Operator Interface Station. Refer to the appropriate instruction manual for complete information relating to these devices.
EAGLEVISION™ OIS POWER SUPPLY DET-TRONICS FLAME DETECTION DET-TRONICS GAS DETECTION 422/232 DET-TRONICS ENVIRONMENTAL MONITORING OR DCS OR NODE 1 NODE 3 NODE 2 NODE 4 NODE 5 PORT (1) PLC COMMUNICATION MODULES (EA2300CM) COMMUNICATION GATEWAY (EA2100CG) PORT (2) DIGITAL COMMUNICATION UNIT (EA2200DCU) NETWORK EXTENDER (EA2400NE) 60 SENSORS AND / OR 2000 METER LOOP A1551 Figure 1—Simplified Eagle System COMMUNICATION GATEWAY – EA2100CG COMMUNICATION MODULE – EA2300CM The gateway provides the
sive calibration. Unlike the communication module, the DCU allows the operator to view three status indicating LEDs through a viewing window on the enclosure cover. NETWORK OPERATION DURING A FAULT CONDITION The Eagle system utilizes a unique method for detecting an open or short in the communication network wiring. This state-of-the-art feature minimizes the possibility of a communication breakdown in the event of a wiring fault in the communication loop and can also serve as an aid in troubleshooting.
Section II EA2300CM Communication Module Multiple Wiring Faults In the event of multiple wiring faults, the nodes between the faults will continue to function, but the faults will prevent them from communicating with the main gateway (Figure 4). In this example, nodes 1 to 4 communicate using one gateway port (path A) and nodes 7 and 8 use the other gateway port (path B). Nodes 5 and 6 are unable to report to the gateway because they are isolated by the two wiring faults.
The red LED indicates the various steps of the calibration process. When the calibration begins, the red LED flashes at a 1 Hz rate. When the zero part of the calibration is completed, the LED is on steady. The span gas is then applied to the sensor, the sensor input increases, and the LED flashes at a 1 Hz rate. When the span part of the calibration is completed, the LED is again on steady.
OUTPUTS Calibration Log A 5 ampere SPDT relay is provided. When the communication module is used with a U8700 or U8800, the relay output is used to reset the transmitter. The relay is actuated for 1 second when a “reset sensor” signal is sent to the communication module by the gateway in response to a request from the host. A log is kept for each calibration. This information can be used by the operator to evaluate the remaining life of a sensor.
MAGNETIC SWITCH * FEATURES EARTH GROUND TERMINAL • • • • • • • R EL AY 12 9 13 8 14 7 15 6 16 5 17 4 18 3 2 1 R EL AY GND 11 10 M AR Y AL ELA R • • • • Field addressable Fault isolation Pass through communication circuitry on power loss 10 bit signal resolution 2 alarm setpoints Sealed 5 ampere SPDT relay Non-volatile memory for logging of alarm and calibration events Non-intrusive one person calibration LED for calibration, fault and alarm status annunciation EMI hardened Screw te
4.5 (11.4) 4.1 (10.4) ENCLOSURE 0.3 DIA. (0.8) 3.38 (8.4) The explosion-proof, watertight aluminum enclosure is designed for use in Class I, Division 1, Groups B, C and D hazardous locations. It is designed to meet CENELEC requirements for EEx d IIC T5 hazardous locations, and is IP66 and NEMA 4 rated. The removable cover is furnished with a window to allow the operator to view the three status indicator LEDs on the communication module PC board.
Section IV EA2100CG Communication Gateway HUMIDITY RANGE— 0 to 90% RH, non-condensing. SHIPPING WEIGHT (Approximate)— 2.6 lb (1.2 kg). APPLICATION DIMENSIONS— See Figure 9. The gateway provides the communication link between a Det-Tronics addressable detector and the host device. Registers in the gateway are used for passing information between the host and communication modules. The gateway communicates with the host device through a serial interface port (RS232 or RS422) using Modbus protocol.
AUXILIARY GATEWAY Digital Display Auxiliary gateways are used to connect additional host devices to the loop for data acquisition purposes. Additional host devices are not able to modify configuration information for the devices on the loop. The digital display is a three digit “seven segment” display. During normal operating conditions, the display indicates “000.
Table 1—Detector Type Codes 01 02 03 04 05 06 07 08 18 19 GAS Ex H2S CL2 CO NH2 SO2 HCL HCN Toxic O2 20 21 22 FLAME UV IR UV/IR LEDs Five faceplate LEDs are provided for indicating the status of the gateway relays. The LEDs correspond to the active state of the relay, not the coil condition. When the relay is reset, the corresponding LED is also reset. RELAYS The gateway is provided with five relays. The relays are sealed and have form C (SPDT) contacts rated 5 amperes resistive at 30 vdc/250 vac.
of the gateway and set the fault bit in the gateway status word in the event of a problem. A watchdog timer resets the gateway if its software gets caught in a loop. HOST MULTIPLEXER In the second form of diagnostics, the gateway provides a watchdog timer for each configured device on the loop. Each time the device reports to the gateway, the timer accumulator is reset to zero and the timer starts over.
GENERAL INFORMATION HUMIDITY— 0 to 95% RH at 70°C. SYSTEM CAPACITY WIRING— The communication network requires 22 AWG level 4 shielded twisted pair wire. Other wiring should be 18 AWG minimum. Eagle system technology allows the main gateway to support a communication loop consisting of up to 60 detection nodes, with up to 2000 meters of connecting wiring.
HOST NODE NODE NODE NODE GATEWAY NODE NODE NODE NODE NODE NODE NETWORK EXTENDER NETWORK EXTENDER NODE NODE NODE NODE NODE NODE NODE NODE NODE NODE TOTAL LOOP CAPACITY: 180 NODES, 6000 METERS NODE A1597 Figure 13—Expanded System with Two Network Extenders NODE HOST HOST MAIN GATEWAY AUXILIARY GATEWAY NODE NODE NODE Section VI EA2500RM Relay Module APPLICATION NODE A1598 The Eagle Relay Module monitors a selected group of detection nodes on the digital communication loop.
Table 4—Status Conditions Capable of Actuating Relay OUTPUTS— One SPDT sealed relay, rated 5 amperes resistive at 30 vdc, programmable for normally energized or normally de-energized operation. Communication Module Status Word Bit Condition 1 2 3 4 5 6 7 8 Com 1 Fault Com 2 Fault Sensor Fault Calibration Alarm 1 Alarm 2 Digital Input 2 Output Relay POWER CONSUMPTION— 60 ma nominal, 80 ma maximum at 24 vdc during normal operation with relay energized.
All external wiring is connected to screw terminal connectors on the terminal wiring board that is factory mounted inside the enclosure. The electronic module is mounted inside the enclosure above the terminal wiring board and is connected to the terminal wiring board with a ribbon cable. ADDRESSABILITY Relay module identification is accomplished by setting rocker switches on an eight position DIP switch located on the electronic module. Valid addresses are from 5 to 110.
NODE GATEWAY NODE NODE NODE NODE “breathing.” Moisture in the air can condense at the base of vertical conduit runs and equipment enclosures, and can build up over a period of time. This can be detrimental to electronic devices. To eliminate this condition, explosion-proof drains and breathers should be installed to automatically bleed off accumulated water. Always observe the requirements of local codes. NOTE Any deviation from the recommended wiring practices can compromise system operation.
Temperature. Resistance increases as operating temperature rises. Calculate resistance at a worst case temperature of 75˚C. See Table 5. Example B: How many combustible gas DCUs can operate at the end of a 1000 foot length of 14 AWG wire? Type of device. Refer to the “Specifications” section for current ratings. Always consider the maximum (not nominal) current draw of each device. This typically occurs at startup and/or when relays are energized.
COMMUNICATION MODULE AND DCU WIRING 1 A 2 B 3 A 4 B 5 + 6 + NETWORK IN 1. Determine the best mounting locations for the detectors. Whenever practical, detectors should be placed where they are easily accessible for calibration. Gas sensors should be pointing down to minimize the accumulation of contaminants on the filter and to ensure proper operation. Junction boxes should be electrically connected to earth ground.
GATEWAY/ COM MOD CHASSIS GROUND 1 2 3 4 5 6 7 8 9 A B NETWORK IN A B + + – – + – DETECTOR POWER (24 VDC) 4 TO 20 MA IN NETWORK OUT DIGITAL INPUT 2 24 VDC POWER INPUT DIGITAL INPUT 1 IN 2 COM IN 1 COM NC RELAY RELAY COMMON NO 18 ALARM 17 ALARM 16 CALIBRATE 15 CALIBRATE 14 FAULT 13 FAULT 12 + 11 – POWER 10 SENSOR RESET COMMUNICATION MODULE – + 4 TO 20 MA EAGLE U8700 (JUMPERED FOR NON-ISOLATED CURRENT OUTPUT) CHASSIS GROUND 1 2 3 4 5 6 7 8 9 A B NETWORK IN A B + + – – + –
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 24 VDC 422 TXD + C 422 TXD – K1 CHASSIS GND + – NO NC C 24 VDC K2 NO 422 RXD + NC 422 RXD – C EXT RESET K3 COM NO NC 232 TXD C 232 RXD K4 COM A B A NO NC C NET 0 FAULT NET 1 NO NC B CHASSIS GND + – 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 GATEWAY 1 2 3 4 5 6 7 8 9 SENSOR CHASSIS A B NETWORK IN A B + + – – + – DETECTOR POWER (24 VDC) 4 TO 20 MA IN NETWORK OUT DIGITAL INPUT 2 24 VDC POWER INPUT DIGITAL INPUT 1 RELAY RELA
1 2 3 4 5 6 7 8 9 A B DETECTOR POWER (24 VDC) NETWORK IN A B + + – – + – 4 TO 20 MA IN NETWORK OUT DIGITAL INPUT 2 24 VDC POWER INPUT DIGITAL INPUT 1 RELAY RELAY COMMON IN 2 COM IN 1 COM NC NO 18 17 16 + – POWER 4 TO 20 15 RED WHITE NC SENSOR BLACK 14 13 GAS TRANSMITTER 12 11 10 COMMUNICATION MODULE/DCU 1 2 3 4 5 6 7 8 9 A B DETECTOR POWER (24 VDC) NETWORK IN A B + + – – + – 4 TO 20 MA IN NETWORK OUT DIGITAL INPUT 2 24 VDC POWER INPUT DIGITAL INPUT 1 RELAY RELAY COMMON IN 2
23 95-8424 24 VDC – + 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 24 VDC POWER INPUT NETWORK OUT NETWORK IN 24 VDC POWER INPUT NETWORK OUT NETWORK IN 24 VDC POWER INPUT NETWORK OUT NETWORK IN GATEWAY + – NO NC COM IN 1 COM IN 2 IN 2 NO NC COM IN 1 COM 10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18 + – + – – U7652C4 + + – + – 20 19 18 17 16 15 14 13 12 11 END OF LINE
RACK TYPE PART NUMBER 005269-XXX CONTROLLER POSITIONS FOR: FIRE GAS HT: DIM. (A) DIM. (B) DIM. (C) INCH DIM. (D) INCH MM INCH MM MM 4U 19.00 482.6 18.30 464.8 17.36 440.9 DIM. (E) WEIGHT INCH MM INCH MM LB KG 4.00 101.6 6.97 177.1 9.3 4.2 4U –001 8 16 4U –002 6 12 4U 15.06 382.6 14.36 364.7 13.42 340.9 7.6 3.5 4U 4U –003 –004 4 3 8 6 4U 4U 11.13 9.16 282.6 232.7 10.43 8.46 264.9 214.9 9.49 241.1 7.52 191.0 5.9 5.1 2.7 2.3 4U –005 2 4 4U 7.
25 95-8424 A1648 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 24 VDC NET 1 NET 0 NC NO C NC NO C NC NO C NC NO CHASSIS GND FAULT K4 K3 K2 C NC Figure 24—Gateway Terminal Configuration B A B A COM 232 RXD 232 TXD COM EXT RESET 422 RXD – 422 RXD + – + CHASSIS GND NO 422 TXD – K1 C 422 TXD + 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 A1545 NOTE 3 OIS POWER SUPPLY + – 24 VDC POWER INPUT NETWORK OUT NETWORK IN 24 VDC POWER INPUT NE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 24 VDC 422 TXD + C 422 TXD – K1 CHASSIS GND + – NC C 24 VDC K2 422 RXD + C EXT RESET K3 COM C 232 RXD K4 COM A B NO NC 232 TXD B NO NC 422 RXD – A NO NO NC C NET 0 FAULT NO NC NET 1 CHASSIS GND + – 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 GATEWAY 1 2 3 4 5 6 7 8 9 SENSOR CHASSIS A B DETECTOR POWER (24 VDC) NETWORK IN A B 4 TO 20 MA IN NETWORK OUT DIGITAL INPUT 2 + + – + – 24 VDC POWER INPUT DIGITAL INPUT 1 – RELAY
S8 LON CONFIGURATION 1 2 3 4 5 6 7 Table 6—Baud Rate Selection – Switches S6-1, S6-2, S6-3 8 BAUD RATE MAIN/AUXILIARY GATEWAY (OFF = AUX, ON = MAIN) BACKUP GATEWAY NON-LATCHING GATEWAY RELAYS UNDEFINED UNDEFINED UNDEFINED GATEWAY ADDRESS BIT 1 (MSB) GATEWAY ADDRESS BIT 0 (LSB) 1200 2400 9600 19,200 57,600 38,400 300 4800 S7 MODBUS ADDRESS 1 2 3 4 5 6 7 8 MODBUS ADDRESS BIT 7 (MSB) MODBUS ADDRESS BIT 6 MODBUS ADDRESS BIT 5 MODBUS ADDRESS BIT 4 MODBUS ADDRESS BIT 3 MODBUS ADDRESS BIT 2 MODBU
CALIBRATION Section VIII System Startup To ensure optimum protection, calibration must be performed on a regularly scheduled basis. Since each application is different, the length of time between regularly scheduled recalibrations can vary from one installation to the next. In general, the more frequently a system is checked, the greater the reliability. STARTUP PROCEDURE 1. Output loads that are controlled by the system should be secured (remove power from all output devices) to prevent actuation.
If the calibration is not completed within 12 minutes, the previous calibration values are restored and the calibration is logged as aborted. The calibrate LED flashes at a 4 Hz rate, the calibrate bit in the status word is reset and the calibration fault bit is set. CALIBRATION ALGORITHM A (Type Codes 1, 2, 3, 4) for Gas Detectors Normal Calibration 1. Activate the reed switch or input 1 on the communication module (See Figure 29).
CALIBRATION ALGORITHM A (Type Codes 1, 2, 3, 4) for Environmental Monitors Calibration After Sensor Replacement 1. Open the communication module junction box cover and press the sensor replacement switch. Normal Calibration 2. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating it is ready for the zero input. The calibrate bit in the status word is set. 1. Activate the reed switch or input 1 on the communication module.
If the calibration is not completed within 10 minutes, the previous calibration values are restored and the calibration is logged as aborted. The calibrate LED blinks at a 4 Hz rate, the calibrate bit in the status word is reset, and the calibration fault bit in the status word is set. CALIBRATION ALGORITHM B (Type Codes 5, 6) Normal Calibration 1. Hold the mode select button on the side of the transmitter enclosure for about 10 seconds. (See Figure 30.
CALIBRATION ALGORITHM C (Type Codes 7, 8, 9, 10) Calibration After Sensor Replacement – Combustible Gas Normal Calibration 1. Open the junction box cover and press the sensor replacement switch for about 1 second. 1. Apply the zero gas. (See Figure 31.) 2. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating it is ready for the zero input. The calibrate bit in the status word is set. 2. Activate the reed switch or input 1 for at least 4 seconds.
Calibration After Sensor Replacement – Toxic Gas CALIBRATION ALGORITHM D (Type Codes 11, 12, 13, 14) 1. Open the junction box cover and press the sensor replacement switch for about 1 second. Normal Calibration 2. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating that it is ready for the zero input. The calibrate bit in the status word is set. 1. Apply clean air (20.9% oxygen). See Figure 32. 2. Activate the reed switch or input 1 for at least 4 seconds.
ACCEPT ZERO A1555 ACCEPT SPAN UNCONTROLLED ANALOG SIGNAL 3 SEC 3 SEC 3 SEC REED SWITCH ANALOG IN FRESH AIR LED ACCEPT ZERO A1555 UNCONTROLLED ANALOG SIGNAL Figure 32—Calibration Algorithm "D" 3 SEC CALIBRATION ALGORITHM E IN ONE (Type Codes 23 and 24) ANALOG IN 3 SEC 3 SEC 3. Apply the zero input (4 ma). 4. Activate the reed switch on the communication module. The red LED will blink at a 2 Hz rate while the reed switch is closed. ZERO LED 1. Apply the zero input (4 ma).
Section IX System Maintenance Calibration After Sensor Replacement 1. Open the junction box cover and press the sensor replacement switch. ROUTINE MAINTENANCE 2. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating it is ready for the zero input. The calibrate bit in the status word is set. To ensure reliable protection, it is important to check and calibrate the system on a regularly scheduled basis.
CAUTION The O-ring should be lubricated with a silicone free polyalphaolefin grease. The use of other lubricants is not recommended, since they can adversely affect the performance of some sensors. Under no circumstances should a lubricant or compound containing silicone be used on systems using catalytic type combustible gas sensors.
Det-Tronics France La Valette Rue du Cimetiere 78790 Septeuil FRANCE Telephone 33 1 3497 0650 Facsimile 33 1 3497 0648 117333 Moscow Gubkina St, d.
ORDERING INFORMATION REFERENCE LIST For assistance in ordering or designing an Eagle system, contact the nearest Detector Electronics office.
DETECTOR ELECTRONICS CORPORATION 6901 West 110th Street Minneapolis, Minnesota 55438 USA Telephone (612) 941-5665 or (800) 765-FIRE Facsimile (612) 829-8750 Telex 6879043 DETEL UW Cable Detronics Printed in USA