Owner's manual

Lower display indicates a “1.” (If any other num-
ber appears, refer to the “Troubleshooting” sec-
tion of this manual.)
2. Push and hold the TEST/ACCEPT button.
A ZONE OUTPUT LED flashes to indicate the
zone of the detector being tested.
Upper left display goes blank.
Lower display changes to “6” to indicate that the
fire threshold has been exceeded due to the radi-
ation received from the UV source in the detector.
(See Table 1 for System Status Codes.)
3. Release the TEST/ACCEPT button.
— The ZONE OUTPUT LED remains on steady.
The upper left display again shows the detector
being checked. The lower display changes back
to a “1.”
4. Push the SELECT button. The controller sequences
to the next lower numbered zone.
NOTE
The
o
i
test will check the detectors connected to
the No. 2 position of each zone first. The upper dis-
play will indicate 2-8, 2-7, etc., and then cycle to 1-
8, 1-7, etc., until all (switch selected) detectors are
checked.
5. Repeat the test until all detectors have been
checked.
6. Return the system to the normal operating mode
after the test is complete.
NOTE
The Automatic
o
i
system continuously monitors the
operation of the R7404 but does not monitor exter-
nal relays or equipment that may be operated from
the fire signal output, the alarm signal output, or the
fault signal output. It is important that the system
be manually checked using the NORMAL mode
checkout procedure on a regular basis. The whole
system (including external equipment) should be
checked periodically using a UV Test Lamp to sim-
ulate a fire.
19 95-8242
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
+
(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1 o
i
DRIVER
D1-2 o
i
DRIVER
D1-3 o
i
DRIVER
D1-4 o
i
DRIVER
D1-5 o
i
DRIVER
D1-6 o
i
DRIVER
D1-7 o
i
DRIVER
D1-8 o
i
DRIVER
D2-1 o
i
DRIVER
D2-2 o
i
DRIVER
D2-3 o
i
DRIVER
D2-4 o
i
DRIVER
D2-5 o
i
DRIVER
D2-6 o
i
DRIVER
D2-7 o
i
DRIVER
D2-8 o
i
DRIVER
DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE
DMA IN AVAILABLE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8
FIRE LOGIC “A”
FIRE LOGIC “B”
ALARM OUTPUT
EXTERNAL RESET/INHIBIT
OUTPUTS INHIBITED
FAULT OUTPUT
EXTERNAL ACCEPT
STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8
DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7
CHASSIS (EARTH) GND
A
B
C
D
C7050
ZONE 1
A
B
C
D
C7050
ZONE 3
A
B
C
D
C7050
ZONE 4
A
B
C
D
C7050
ZONE 5
A
B
C
D
C7050
ZONE 6
FIRE ALARM CONTROL CABINET
B0873
0.47 uf, 250 VDC
NON-POLARIZED
J2
R7404J1
10 TO 38 VDC
}
A
B
C
D
C7050
ZONE 2
A
B
C
D
C7050
ZONE 7
A
B
C
D
C7050
ZONE 8
A
B
C
D
A
B
C
D
C7050
ZONE 1
A
B
C
D
C7050
ZONE 3
A
B
C
D
C7050
ZONE 4
A
B
C
D
C7050
ZONE 5
A
B
C
D
C7050
ZONE 6
A
B
C
D
C7050
ZONE 2
A
B
C
D
C7050
ZONE 7
A
B
C
D
C7050
ZONE 8
A
B
C
D
J1-3
J1-5
J1-2
J1-13
A
B
C
D
J1-3
J1-4
J1-2
J1-20
A
B
C
D
J1-3
J1-5
J1-2
J1-21
A
B
C
D
J1-3
J1-6
J1-2
J1-14
A
B
C
D
J1-3
J1-6
J1-2
J1-22
A
B
C
D
J1-3
J1-7
J1-2
J1-15
A
B
C
D
J1-3
J1-7
J1-2
J1-23
A
B
C
D
J1-3
J1-8
J1-2
J1-16
A
B
C
D
J1-3
J1-8
J1-2
J1-24
A
B
C
D
J1-3
J1-9
J1-2
J1-17
A
B
C
D
J1-3
J1-9
J1-2
J1-25
A
B
C
D
J1-3
J1-10
J1-2
J1-18
A
B
C
D
J1-3
J1-10
J1-2
J1-26
A
B
C
D
J1-3
J1-11
J1-2
J1-19
A
B
C
D
J1-3
J1-11
J1-2
J1-27
Figure 24—A Typical System – 16 Detectors in 8 Zones