Owner's manual

The Data Bus terminals (56 to 63) and the DMA (direct
memory access) and Data Strobe terminals (28 to 32)
provide external access to the microprocessor, which
permits inter-controller communication. For further infor-
mation, contact the Field Support Group at Detector
Electronics. (This feature is not available on all R7404
models.)
STARTUP PROCEDURE
CAUTION
Placing the controller in the Test mode inhibits its out-
puts, rendering the system incapable of actuating any
extinguishing or alarm circuits that are connected to it.
For maximum safety, however, secure output loads
(remove power from any devices that would normally
be actuated by the system) before manually testing
the system. Remember to place this same equip-
ment back into service when the test is complete.
1. After setting the selection switches and making all
electrical connections, plug the controller into the
connector.
2. Turn on power and perform Checkout Procedure.
3. If the controller appears to be operating normally,
remove mechanical blocking devices and restore
power to the extinguishing loads.
NOTE
Be sure that the detector is correctly aimed at the
potential hazard and that no obstructions interfere
with its line of vision. In addition, UV absorbing
gases should not exist between the detector and
the potential hazard.
CHECKOUT PROCEDURE
CAUTION
When testing the system, be sure to secure all output
devices to prevent unwanted activation of this equip-
ment, and remember to place these same devices
back into service when the checkout is complete.
MANUAL o
i
CHECK
1. Place the keylock switch in the TEST position.
The FAULT and INHIBIT LEDs turn on
Upper right display indicates the zone selected.
Upper left display identifies the detector of the
displayed zone.
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
+
(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1 o
i
DRIVER
D1-2 o
i
DRIVER
D1-3 o
i
DRIVER
D1-4 o
i
DRIVER
D1-5 o
i
DRIVER
D1-6 o
i
DRIVER
D1-7 o
i
DRIVER
D1-8 o
i
DRIVER
D2-1 o
i
DRIVER
D2-2 o
i
DRIVER
D2-3 o
i
DRIVER
D2-4 o
i
DRIVER
D2-5 o
i
DRIVER
D2-6 o
i
DRIVER
D2-7 o
i
DRIVER
D2-8 o
i
DRIVER
DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE
DMA IN AVAILABLE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8
FIRE LOGIC “A”
FIRE LOGIC “B”
ALARM OUTPUT
EXTERNAL RESET/INHIBIT
OUTPUTS INHIBITED
FAULT OUTPUT
EXTERNAL ACCEPT
STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8
DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7
CHASSIS (EARTH) GND
A
B
C
D
C7050
ZONE 1
A
B
C
D
C7050
ZONE 2
A
B
C
D
C7050
ZONE 3
A
B
C
D
C7050
A
B
C
D
C7050
FIRE ALARM CONTROL CABINET
A
B
D
A
B
D
J1-3
J1-5
J1-21
A
B
D
J1-3
J1-4
J1-20
A
B
D
JI13
J1-5
J1-13
A
B
D
J1-3
J1-6
J1-22
C0286
J2
R7404J1
10 TO 38 VDC
}
A
B
C
D
C7050
A
B
D
J1-3
J1-6
J1-14
ALTERNATE METHOD OF TERMINATING SHIELDS,
FOR USE WHERE CODES PERMIT
Figure 23—Typical System - Six Detectors in Three Zones