Owner's manual

17 95-8242
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
+
– 
(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1 o
i
DRIVER
D1-2 o
i
DRIVER
D1-3 o
i
DRIVER
D1-4 o
i
DRIVER
D1-5 o
i
DRIVER
D1-6 o
i
DRIVER
D1-7 o
i
DRIVER
D1-8 o
i
DRIVER
D2-1 o
i
DRIVER
D2-2 o
i
DRIVER
D2-3 o
i
DRIVER
D2-4 o
i
DRIVER
D2-5 o
i
DRIVER
D2-6 o
i
DRIVER
D2-7 o
i
DRIVER
D2-8 o
i
DRIVER
DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE
DMA IN AVAILABLE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8
FIRE LOGIC “A”
FIRE LOGIC “B”
ALARM OUTPUT
EXTERNAL RESET/INHIBIT
OUTPUTS INHIBITED
FAULT OUTPUT
EXTERNAL ACCEPT
STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8
DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7
CHASSIS (EARTH) GND
A
B
C
D
C7050
ZONE 1
A
B
C
D
C7050
ZONE 2
A
B
C
D
C7050
ZONE 3
A
B
C
D
C7050
ZONE 4
A
B
C
D
C7050
ZONE 5
FIRE ALARM CONTROL CABINET
A
B
C
D
A
B
C
D
J1-3
J1-7
J1-2
J1-15
A
B
C
D
J1-3
J1-5
J1-2
J1-13
A
B
C
D
J1-3
J1-6
J1-2
J1-14
A
B
C
D
J1-3
J1-8
J1-2
J1-16
C0285
0.47 uf, 250 VDC
NON-POLARIZED
J2
R7404J1
10 TO 38 VDC
}
Figure 22—Typical System - Five Detectors in Five Zones
Table 4—Relationship of SYSTEM STATUS Display to
Status Outputs
Table 3—Relationship of Zone and Detector Displays to the
Status Outputs
Front Panel Display Status Outputs
Zone Detector S1 S2 S3 S4 S5
1 1 10000
1 2 10001
2 1 01000
2 2 01001
3 1 11000
3 2 11001
4 1 00100
4 2 00101
5 1 10100
5 2 10101
6 1 01100
6 2 01101
7 1 11100
7 2 11101
8 1 00010
8 2 00011
Front Panel Display Status Outputs
Outputs
System Status S6 S7 S8 Fault Inhibited
0 000 0 1
1 100 0 1
2 010 0 0
3 110 1 0
4 001 0 0
5 101 0 0
6 011 1 0
7 111 0 1
8 000 0 1
Blank and No Fault 0 0 0 1 0
Status Outputs Logic 0 =100 kilohms to 0 volts
S1 – S8, Fault Logic 1 = Less than 25 ohms to
Outputs Inhibited 0 volts