appenDix D
IECEx APPROVAL DESCRIPTION
IEC Standards:
IEC60079-0: 2011 Electrical apparatus for explosive atmospheres, General Requirements
IEC60079-1: 2007 Electrical apparatus for explosive atmospheres, Flameproof enclosure “d”
IEC60079-11: 2011 Intrinsic Safety explosive atmospheres Equip protection by Intrinsic Safety
IEC60079-31: 2008 Explosive atmospheres Equip. Dust Ignition Protection by enclosure “t
IEC60529: 2001 Degrees of Protection Provided by Enclosures (IP Code)
IEC Special Conditions for Safe Use (X):
AC100
• TheAC100AcousticSensormustalwaysbeinstalledwiththedetectionheadpointingdownvertically.
• TheAC100AcousticSensormustonlybeinstalledinareaswherethereisalowriskofmechanicaldamage.
•
The AC100 is only to be used connected to the ATX10 Acoustic Transmitter or Model STB Sensor Termination Box.
ATX10
• TheATX10mustonlybeinstalledinareaswherethereisalowriskofmechanicaldamage.
Warning
Always ensure that the detector/junction box hazardous (classied) location ratings are applicable for the
intended use.
Additional Safety Notes:
• The followingwarning ison theproduct:Warning:Do notopenwhenan explosivegasatmospheremaybe
present. For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For
temperature below –10°C use suitable field wiring for the lowest temperature.
• Cable,bushingsandtheconduitentriesshallbeofaameprooftypealreadycertiedaccordingtorelevantIEC
standard, rated IP66, so the protection principle employed will not be impaired.
• Unusedconduitentries shallbeclosedusingameproofstopplugscertiedfortheconditionsofuse(IP66
minimum). The stop plugs should be removable only with the aid of a tool.
• Shieldedcableisrequired.
AC100
IECEx ULD13.0002X
Ex d ib IIC T4 Gb
Ex tb IIIC T80°C Db
T
amb:
5C to +75°C
IP66
ATX10
IECEx ULD13.0003X
Ex d IIC T6 Gb
Ex tb IIIC T80°C Db
T
amb:
5C to +75°C
IP66