Specifications
60
Interior Delay #2: Same as Exterior Delay #2 except active only in AWAY and NIGHT mode
and no monitor is provided. Uses delay time #2.
Panic: Panic zones respond with a high volume alert on both the internal and external
speaker. The alert consists of a pulsed tone followed by "ALERT, ALERT", and the up-to-four-
word description of the zone.
Silent Panic: Silent panic zones respond by activating the communicator. An activation
appears in system status, however, no audible indication is given.
Step Arming: The arm/disarm zone type is used for momentary arming inputs such as a
keyswitch or touchpad. Each time the zone is closed the system moves in order between
the following stages. Starting with the system disarmed, the first momentary closure will
arm the system to AWAY. A second momentary closure, before exit delay time expires, will
arm the system to HOME. A second closure after exit time has expired, will disarm the
system. Arming to NIGHT is not available if an arm/disarm zone is used. Even if force
arming is not programmed, the system will always force arm any open zones when an arm/
disarm zone is used. This option is not permitted in UL installations.