Specifications

59
Zone type assignment: Auxiliary: Auxiliary zones are non-burglary zones designed to provide an automation,
information, or service input to the system. This zone type does not activate an alarm
even when the system is armed. When monitor mode is active, the zone is
programmed to show open/close status at keypad and speak auxiliary zone type
(System Option - Group 5, option 001) is enabled, the system will speak the zone
description or sound a monitor beep when the zone input is activated. An auxiliary
zone can be programmed to alert the central station.
Day: When the system is not armed a Day zone will cause an Extended Monitor
activation and can send a Day Zone Trouble report to the central station. When the
system is armed a Day Zone will act like an Exterior Instant. A day zone extended
monitor activation can be cancelled with the "Silence Day Zone" button function.
Emergency: Emergency zones respond though inside speakers only. The alert
consists of a pulsed tone followed by "ALERT, ALERT", and the up-to-four-word
description of the zone.
Exterior Instant: Exterior instant zones instantly sound an alarm when the system is
armed to HOME, AWAY or NIGHT. When the system is not armed, monitor mode is
active, and the zone is programmed to show open/close status at the keypad, the
system will speak the zone description or sound a monitor beep when the zone input
is activated. Exterior Instant zones can be programmed to sound an alarm when the
input is activated during an exit delay (System Options - Group 2, option 008).
Otherwise, the exterior instant zone will respond in the same manner as when the
system is not armed.
Exterior Delay #1: Tripping an exterior delay input places the system into a pre-
alarm mode if the system is armed to AWAY or HOME (unless "No entry delay for
Exterior Delay #1 in Home" is selected in System Options - group 2). The system
refers to entry delay time #1 to determine the pre-alarm duration. If pre-alarm expires
without a user entering a valid disarm code, the system will sound an alarm. When
the system is not armed, monitor mode is active, and the zone is programmed to show
open/close status at keypad, the system will speak the zone description or sound a
monitor beep when the zone input is activated. During an exit delay, Exterior Delay
zones respond in the same manner as when the system is not armed. In Night mode,
this zone type acts an exterior instant.
Exterior Delay #2: Same as above but uses programmable entry delay time #2.
Fire: Fire zones respond with short high volume tones over the internal and external
speakers. The system will alternate between the tones and speaking "FIRE, FIRE,"
followed by the up-to-four-word zone description, and "REMAIN CALM, LEAVE
IMMEDIATELY."
Follower: An interior follower zone is active in the AWAY mode only. A follower
acts as an instant zone providing an exterior delay zone is not previously tripped.
When the system is in pre-alarm, the follower follows the pre-alarm time. No monitor
function is provided and during an exit delay, an opening is ignored.
Interior Instant: The interior instant zones are active in the AWAY mode only. No
monitor function is provided for interior zones (except during extended monitor).
During an exit delay, an opening is ignored.
Interior Delay #1: Same as Exterior Delay #1 except active only in AWAY mode and
no monitor is provided.