Specifications

34
Extended Monitor Zone Type Assignment
Zone Types - Enter Total for Extended Monitor A Location Value
Exterior instant
..............................................................................................................................
001
Exterior delay 1
............................................................................................................................
002
Exterior delay 2
............................................................................................................................
004
Interior instant
...............................................................................................................................
008
Interior delay 1
.............................................................................................................................
016
Interior delay 2
.............................................................................................................................
032
Follower
........................................................................................................................................
064
Auxiliary 1 and 2
..........................................................................................................................
128
Default
.........................................................................................................................
0177
.......
001
Zone Types - Enter Total for Extended Monitor B Location Value
Exterior instant
..............................................................................................................................
001
Exterior delay 1
............................................................................................................................
002
Exterior delay 2
............................................................................................................................
004
Interior instant
...............................................................................................................................
008
Interior delay 1
.............................................................................................................................
016
Interior delay 2
.............................................................................................................................
032
Follower
........................................................................................................................................
064
Auxiliary 1 and 2
..........................................................................................................................
128
Default
.........................................................................................................................
0178
.......
007
With the system disarmed, entering a full function user code followed by the 3 or 4 digit, will place the system
into extended monitor mode A or B. The system will speak "MONITOR ON" through the inside speaker.
Entering a full function user code followed by 3 or 4 will clear any active extended monitor zones and stop the
extended monitor beep or speech. The system will speak "MONITOR RESTORED." If the system is in extended
monitor mode and there are no extended monitor zones active, entering a full function user code followed by 3
or 4 will take the system out of extended monitor mode. The system will speak "MONITOR OFF".
The enunciation feature of the control panel can be used to monitor exterior, interior, and follower zones. As an
example, it may be desirable to monitor interior door activity of residents in a retirement home. Normal
extended monitor activity is not sent to the central station. If a Day Zone causes an Extended Monitor activation
when the system is not armed, a Day Zone Trouble can be sent to the central station.
There are two different levels or types of extended monitor, A and B. Locations 0177 and 0178 determine which
zone types are to be monitored by each extended monitor type. Entering a full function user code followed by
the digit 3 will place the system in extended monitor mode type A or enter the 4 digit for extended monitor type
B. When entering extended monitor the system responds with "MONITOR ON" through the inside speaker.
NOTE: You can only enter the extended monitor mode when the system is disarmed. If the system is in extended
monitor mode it will automatically exit that mode when the system is armed.
Fail To Open (Disarm) / Fail to Close (Arm)
Options - Enter Total Location Value
Enable Fail to Open
......................................................................................................................
001
Fail to Close - Verify Armed to AWAY
..........................................................................................
002
Fail to Close - Verify Armed to Home or Night
...........................................................................
004
Fail to Close - Verify Armed to AWAY, Home or Night
................................................................
008
Use 5 day cycle (otherwise 7 day cycle)
.....................................................................................
016
Default (Fail to Open / Close disabled)
.....................................................................
0216
.......
000
Fail to open/close will check system arming status at a programmed time and report to the central station if the
proper condition is not met. Program the option total in location 0216. Use location 9994 to program the
appropriate fail to Arm time followed by the Disarm time in military format. For times below 10:00 use a
leading zero. If only one arming state is being monitored, you must still enter two times. If the option is not
selected the programmed time will be ignored.