Instruction Manual
38
Technical Specifications
UL, cUL listed: UL file E136675
CE compliance to:
• EMC Directive 89-366/EEC
• European Standard EN55011/1991
• European Standard EN50082-2/1995
Power supply:
• 100 to 240 VAC +10% -15%, 50-60Hz, 30VA Maximum
• 12 to 24 VAC/VDC +/-10%, DC to 60Hz, 30VA Maximum
Temperature:
• Storage -20 to 60°C
• Operating 0 to 50°C
Humidity: 90% or less, non-condensing
Sensor inputs:
• Type J thermocouple
-73°C to 760°C (-100°F to 1400°F)
• Input impedance 1M ohm or greater
• Common mode noise rejection of 140db@60Hz
• Common mode input voltage of +/-12.0VDC
• Sample rate of at least 1 sample per second
• Stability of +/- 0.5ΕC per 5ΕC change in ambient temperature
• Repeatability of +/- 0.5ΕC, or +/-0.1% of sensed temperature (whichever is
greater)
• Accuracy (@ 77
°F +/-0.2 percent of span (+/-3°F)
• Supply Voltage Influence of +/-0.5ΕC per 10% change in nominal line voltage
Temperature
display:
• 1 degree resolution (C or F)
• Accuracy after calibration of +/- 1ΕC, or +/-0.2% of sensed temperature
(whichever is greater) @25ΕC
• Four-digit seven-segment LCD, 0.43 inches high (11mm)
• Readout Stability (+/-
1°F/10°F Change in ambient temperature)
Message display:
• Two-line, 16 alpha-numeric 5x7 dot matrix characters per line
• 0.2 inches high (5mm)
Time base: +/- 4 seconds accuracy in 24 hours
Heat control output: SSR Drive 24VDC nominal @ 70mA
Cooling control output: 4-20ma DC > 0-800 Ohm Load
Relay output: (plug-in
module)
Form A dry contact, rated 3 amps @ 24-264VAC
Communications:
(plug-in module)
• RS232 Single drop, isolated
• RS422 Multi-drop, isolated
• RS485 Multi-drop, isolated
Remote inputs:
(plug-in module)
Dry-contact closure type with less than 250 ohm ON resistance
Front panel: NEMA 4X (with gasket)
Dimensions: 3.57H x 7.24W x 2.84D inches (91H x 184W x 72D mm)