5.11. Setting Up Digital Inputs
The Protocol 3 controller can be run by external inputs wired to the controller from an external
source such as a PLC or switches on a control panel (Figure 21 displays standard digital input
wiring).
Enable Digital Inputs through the Profile Menu, then General Configuration and set Remote
Profile Control to Enable.
While the Remote Profile Control is enabled, profiles can be run
only by digital inputs (versus running profiles from the Profile
Mode).
The external run operation can Run, Hold or Stop profiles indexed in positions 1-7 in the
memory of the control. Table 19 shows the profile selection.
Table 19. Input settings.
Input 1
Input 2
Input 3
Index Selection
ON
OFF
OFF
1
OFF
ON
OFF
2
ON
ON
OFF
3
OFF
OFF
ON
4
Figure 21. Standard Digital Input Wiring.